505429-JTG-L-0512
Johnson Controls Unitary Products 21
115°F 125°F
3000
77 117.5 12.0 63.4 50.4 37.4 - - - 108.0 13.2 60.3 47.2 34.1 - - -
72 109.1 11.9 81.0 68.0 55.0 41.9 - - 101.2 13.2 78.4 65.3 52.2 39.1 - -
67 100.8 11.9 98.6 85.6 72.6 59.5 46.5 - 94.3 13.1 94.3 83.4 70.3 57.2 44.1 -
62 94.0 11.8 94.0 94.0 89.4 76.4 63.4 50.4 87.2 13.0 87.2 87.2 85.1 72.0 59.0 45.9
57 94.0 11.8 94.0 94.0 84.7 71.7 58.7 45.7 87.8 13.1 87.8 87.8 77.8 64.7 51.7 38.6
3500
77 124.2 12.0 74.4 55.8 41.1 - - - 115.1 13.2 73.6 53.0 38.1 - - -
72 115.4 11.9 89.9 75.2 60.4 45.7 - - 107.7 13.2 87.9 73.1 58.2 43.4 - -
67 106.6 11.9 105.5 94.6 79.8 65.1 50.3 - 100.4 13.1 100.4 93.2 78.3 63.5 48.6 -
62 99.4 11.8 99.4 99.4 98.4 83.6 68.9 54.1 92.8 13.0 92.8 92.8 92.8 80.4 65.2 50.3
57 99.4 11.8 99.4 99.4 93.2 78.5 63.7 49.0 93.5 13.1 93.5 93.5 86.9 72.4 57.2 42.3
4000
77 131.0 12.0 85.5 61.3 44.8 - - - 122.1 13.2 86.9 58.7 42.1 - - -
72 121.7 11.9 98.9 82.4 65.9 49.5 - - 114.3 13.2 97.5 80.8 64.2 47.6 - -
67 112.3 11.9 112.3 103.5 87.1 70.6 54.1 - 106.5 13.1 106.5 103.0 86.3 69.7 53.1 -
62 104.8 11.8 104.8 104.8 107.3 90.8 74.4 57.9 98.5 13.1 98.5 98.5 98.5 88.7 71.4 54.8
57 104.8 11.8 104.8 104.8 101.7 85.2 68.7 52.2 99.2 13.1 99.2 99.2 95.9 80.1 62.7 46.0
4500
72 124.7 11.9 107.6 89.3 71.0 52.8 - - 116.1 13.2 106.1 87.5 68.9 50.3 - -
67 115.2 11.9 115.2 110.8 93.8 75.5 57.2 - 108.2 13.1 108.2 108.2 92.6 74.0 55.4 -
62 107.4 11.8 107.4 107.4 108.7 90.4 72.1 53.8 100.0 13.1 100.0 100.0 100.0 84.9 65.9 47.3
57 107.4 11.8 107.4 107.4 105.9 87.6 69.3 51.0 100.7 13.1 100.7 100.7 99.1 80.9 61.9 43.3
5000
72 127.8 12.0 116.3 96.2 76.1 56.1 - - 117.9 13.2 114.7 94.1 73.6 53.0 - -
67 118.0 11.9 118.0 118.0 100.5 80.4 60.4 - 109.9 13.1 109.9 109.9 98.9 78.4 57.8 -
62 110.1 11.8 110.1 110.1 110.1 90.0 69.9 49.8 101.6 13.0 101.6 101.6 101.6 81.0 60.4 39.9
57 110.1 11.9 110.1 110.1 110.1 90.0 69.9 49.8 102.3 13.1 102.3 102.3 102.3 81.7 61.2 40.6
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
J10YC/J10NC (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65

Other manuals for Johnson Controls R-410A

Related product manuals