RL SERIES INSTALLATION MANUAL
RLLV180 - Blower Performance Data
Airflow in CFM with dry coil and clean air filter.
External Static Pressure (in. w.g.)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0
MTR/SHEAVE 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 4.0 4.0
BHP 0.61 0.64 0.66 0.68 0.76 0.81 0.87 0.89 0.94 1.05
RPM 581 601 621 663 703 739 774 784 827 867
TURNS OPEN 5.0 4.5 4.0 3.0 2.0 1.5 1.0 0.5 2.0 1.0
MTR/SHEAVE 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 4.0 4.0
BHP 0.64 0.66 0.71 0.77 0.82 0.85 0.94 0.97 1.04 1.14
RPM 591 611 642 682 712 740 778 795 841 886
TURNS OPEN 4.5 4.0 3.5 2.5 1.5 1.0 0.5 0.0 1.5 0.5
MTR/SHEAVE 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 4.0 4.0 4.0
BHP 0.65 0.66 0.68 0.75 0.86 0.87 0.88 1.02 1.05 1.14 1.23
RPM 580 600 621 662 701 722 742 782 805 855 905
TURNS OPEN 5.0 4.5 4.0 3.0 2.0 1.5 1.0 0.0 2.5 1.5 0.0
MTR/SHEAVE 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 3.0 3.0 3.0 3.0 5.0 5.0
BHP 0.69 0.70 0.76 0.86 0.92 0.93 1.01 1.08 1.11 1.19 1.30 0.74 0.80 0.85
RPM 590 610 641 681 711 731 761 790 809 850 898 470 480 496
TURNS OPEN 4.5 4.0 3.5 2.5 1.5 1.0 0.5 0.0 3.0 2.5 2.0 1.0 3.0 2.5
MTR/SHEAVE 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 3.0 3.0 3.0 3.0 3.0 5.0 5.0
BHP 0.72 0.73 0.74 0.84 0.96 0.98 0.99 1.13 1.14 1.17 1.23 1.36 1.48 1.59 1.69
RPM 579 600 620 660 700 721 741 780 797 813 845 890 940 960 991
TURNS OPEN 5.0 4.5 4.0 3.0 2.0 1.5 1.0 0.0 3.0 2.5 2.0 1.0 0.0 3.0 2.5
MTR/SHEAVE 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 3.0 3.0 3.0 3.0 5.0 5.0 5.0
BHP 0.76 0.77 0.84 0.95 1.02 1.04 1.12 1.20 1.23 1.27 1.36 1.49 1.58 1.72 1.86
RPM 589 609 640 680 710 730 760 788 808 828 868 914 941 963 991
TURNS OPEN 4.5 4.0 3.5 2.5 1.5 1.0 0.5 0.0 2.5 2.0 1.5 0.5 3.5 2.5 2.0
MTR/SHEAVE 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 3.0 3.0 3.0 3.0 3.0 5.0 5.0 5.0
BHP 0.79 0.80 0.82 0.93 1.06 1.08 1.10 1.25 1.26 1.31 1.36 1.49 1.62 1.67 1.85 2.03
RPM 578 599 619 659 699 719 739 778 795 819 843 890 937 942 967 991
TURNS OPEN 5.0 4.5 4.0 3.0 2.0 1.5
1.0 0.0 3.0 2.5 2.0 1.0 0.0 3.0 2.5 2.0
Bold Face Requires Larger 2.0 HP Motor
A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr
Units factory shipped with standard static sheave and drive at 3 turns open (5600 cfm @ 0.6 in. ESP). Other speeds require field selection.
ISO/AHRI rating point with standard static sheave and drive at 1.5 turns open (5600 cfm @ 0.7 in. ESP). Other speeds require field selection.
For applications requiring higher static pressures, contact your local representative.
Performance data does not include drive losses and is based on sea level conditions.
Do not operate in gray region. "na" = information not available at time of printing.
All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12 in. wg.
BHP is given for each blower. Multiply BHP x 2 for unit BHP.
7/25/07
5800
6000
6200
6400
Rated CFM
5200
5400
5600
D
A
C
E
Belt Drive
JOHNSON CONTROLS
24

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls RL Series and is the answer not in the manual?

Johnson Controls RL Series Specifications

General IconGeneral
BrandJohnson Controls
ModelRL Series
CategoryHeat Pump
LanguageEnglish

Related product manuals