RL SERIES INSTALLATION MANUAL
Multistate Input (Type 13)
13:1 Effective Occupancy
[Read, shows the occupancy status of the heat
pump. 1=Occupied, 2=Unoccupied, 3=Bypass
(temporary occupancy)]
13:2 Mode
[Read, shows heat pump as normal or emergency
shutdown 1=Auto(normal), 7=Off(shutdown)]
13:3 Compressor/Blower Prove
[Read, shows the contact status of BI-4.]
Multistate Output (Type 14)
14:1 Occupancy Command
[Read/Write, controls the occupancy mode of the
heat Pump. 1=Occupied, 2=Unoccupied, 3=Bypass
(Temporary Occupancy), 4=Standby,
255=Uncommanded]
14:2 Blower Command (G)
[Read/Write, network command to run the blower]
14:3 Comp1 Command (Y1)
[Read/Write, network Y1 command (compressor
1 call).]
14:4 Comp2 Command (Y2)
[Read/Write, network Y2 command (compressor
2 call).]
14:5 Rev Vlv Cmd (O)
[Read/Write, network O command. 1= heating,
2= cooling.]
14:6 Emergency Override
[Read/Write, provide means of emergency
shutdown]
14:7 Alarm Reset
[Read/Write, allows remote reset of manual reset
alarms, Command to a ‘2’ value for reset action,
1 for normal Operation.]
14:8 BO5 ElectHeat
[Read/Write, network command to enable electric
heat (interlocked with BI4)]
14:9 BO9 Spare
[Read/Write, network command to enable/disable
BO9]
Optional FX10 Microprocessor Control - BACnet Variables
JOHNSON CONTROLS
38

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls RL Series and is the answer not in the manual?

Johnson Controls RL Series Specifications

General IconGeneral
BrandJohnson Controls
ModelRL Series
CategoryHeat Pump
LanguageEnglish

Related product manuals