EasyManua.ls Logo

Johnson Controls SABROE SAB 151 E - User Manual

Johnson Controls SABROE SAB 151 E
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
SAB 120-151 A-frame (including ATEX)
Screw compressor units
Operating manual
en

Table of Contents

Questions and Answers

  • M
    Michael HamiltonSep 12, 2025
    Why does the oil pressure rapidly drop when my Johnson Controls SABROE SAB 151 E starts?
    • A
      Angel ClarkSep 12, 2025
      If the oil pressure rapidly drops off when your Johnson Controls Air Compressor starts, resulting in a compressor differential alarm, the main oil injection throttling valve might be too wide open, or the oil pressure regulating valve may be improperly adjusted. Readjust both valves.
  • E
    Elizabeth SimmonsAug 23, 2025
    Why is the discharge pressure excessively high in my Johnson Controls Air Compressor?
    • C
      collinsphillipAug 23, 2025
      Excessively high discharge pressure in your Johnson Controls Air Compressor can be due to several reasons. The safety cut-out might be set too low, so check the settings of alarms and warnings. There could be high discharge line loss, so inspect the valves. A malfunctioning condenser may also be the cause; check the condenser, liquid drain, refrigerant charge, water/air inlet temperature, and water/air flow. Finally, air or non-condensable gasses in the system can cause this issue, so purge the air from the condenser side.
  • J
    Jessica BarkerAug 25, 2025
    How to fix excessively low suction pressure in Johnson Controls Air Compressor?
    • J
      Jennifer HillAug 25, 2025
      Excessively low suction pressure in your Johnson Controls Air Compressor can be caused by a refrigeration load that's lower than the compressor capacity; in this case, reduce compressor capacity. It could also be due to high suction line loss, so check the valves and strainers. Another cause might be a malfunction of the evaporator, so inspect the evaporator for fouling or accumulated oil. Also, check the liquid expansion valve system, filter in the liquid line, and ensure there is sufficient refrigerant charge.
  • H
    hermantylerAug 26, 2025
    What to do if my Johnson Controls SABROE SAB 151 E has excessive noise and vibration?
    • J
      Jonathan WilsonAug 27, 2025
      Excessive noise and vibration in your Johnson Controls Air Compressor could stem from several issues. The main oil injection valve may be closed or open too far, so open or adjust it accordingly. Bearing damage or excessive wear can also cause this, requiring bearing replacement. Additionally, the slide valve/slide stop might be out of calibration, needing calibration. A loose coupling on the shaft should be tightened or replaced if damaged. Finally, refrigerant flood back (liquid slugging) can lead to these symptoms, so correct the underlying system problem.
  • R
    Renee CollinsAug 29, 2025
    Why won't the capacity slide valve move on my Johnson Controls SABROE SAB 151 E Air Compressor?
    • J
      Joshua MitchellAug 29, 2025
      If the capacity slide valve or slide stop on your Johnson Controls Air Compressor won't move, preventing unloading/loading, it could be due to insufficient oil pressure, so check the oil pressure. The solenoid coils might be burned out, requiring replacement. Incorrect valve settings in the hydraulic system could also be the cause, so check according to the hydraulic system description. Lastly, a malfunction of the 4-way control valve of slide components could be the issue, so check according to the description of main components.
  • J
    James ParrishAug 30, 2025
    What causes high suction pressure and insufficient refrigeration capacity in a Johnson Controls SABROE SAB 151 E Air Compressor?
    • J
      jesus45Aug 31, 2025
      High suction pressure combined with insufficient refrigeration capacity in your Johnson Controls Air Compressor can occur if the compressor protection valve is opening or leaking, so check the discharge pressure safety cut-out settings and the pilot/main protection valve. An oil return valve that is fully open can also cause this issue, so adjust the regulating valve. Finally, a clogged suction strainer can lead to these symptoms, so clean the strainer.
  • F
    fuentesamandaSep 18, 2025
    Why is grease leaking from the vent port of my Johnson Controls SABROE SAB 151 E Air Compressor?
    • A
      Aaron SpearsSep 18, 2025
      Grease leaking from the vent port in the side of the pump body is normal and will cease after initial operation. However, black oil leaking from this vent indicates oil seal wear or failure. If leakage exceeds the normal allowable rate of 7 drops per minute, replace the seal.
  • T
    Thomas NortonNov 26, 2025
    Why is the oil temperature too high in my Johnson Controls SABROE SAB 151 E Air Compressor?
    • B
      Barbara PattersonNov 26, 2025
      High oil temperature in your Johnson Controls Air Compressor, accompanied by high discharge temperature, can be attributed to several factors. Check that the valves in the oil system are fully open. If you have a 3-way oil temperature control valve, check its function and replace the sensor element if needed. For water-cooled systems, check the oil cooler for fouling, water inlet temperature, and water flow. For refrigerant-cooled systems, check/drain accumulated oil in the oil cooler and ensure the gravity-fed refrigerant system is fully flooded. For liquid injection systems, check the settings in the control system, valves, and strainer in the liquid injection line. Also, verify that the compressor protection valve is not open or leaking by checking the discharge pressure safety cut-out ...
  • N
    Nancy RobbinsSep 9, 2025
    What causes gradual oil loss in my Johnson Controls SABROE SAB 151 E?
    • S
      susan73Sep 9, 2025
      Gradual oil loss in your Johnson Controls Air Compressor, with an oil level in the coalescer section sight glass, can be due to maintaining too high an oil level; lower the level by opening/adjusting the oil return valve. It could also be caused by refrigerant carry-over or liquid injection overfeeding, so correct the operation. Loss of suction superheat can also contribute, so adjust evaporator feeds. Contaminated oil or damaged coalescer elements may be the cause, so replace the oil charge and coalescers. A closed coalescer return valve should be opened. Finally, a blocked coalescing oil return line strainer should be cleaned.
  • G
    Gregory RobinsonSep 6, 2025
    Why is the discharge temperature very low in my Johnson Controls Air Compressor?
    • A
      ashleywatersSep 6, 2025
      A very low discharge temperature in your Johnson Controls Air Compressor, accompanied by low oil temperature and potential oil foaming in the oil separator, can be caused by excessive liquid in the suction line or liquid slugging. Check the evaporator and expansion valve function, and decrease the rate of evaporator temperature "pull down." Alternatively, liquid injection may be overfeeding, so check the settings in the control system and the stability of the liquid injection.

Summary

Introduction to Operating Manual

Compressor Name and Frick Identification

Identifies compressor models and their Frick counterparts for the SABROE units.

Safety Precaution Definitions and Requirements

Explains safety warning symbols (Danger, Warning, Caution) and requirements for competent personnel.

Unit and Component Identification Plates

Details the information found on unit, ATEX, and vessel name plates.

Areas of Application and Safety Precautions

Compressor Application Guidelines

Details correct and incorrect uses of the screw compressor and ATEX considerations.

General Safety Precautions

Illustrates and explains all safety signs and general warnings for equipment safety.

Operation and Maintenance Safety

Covers safety during unit operation, maintenance, and service, including ventilation and pressure.

Refrigerant, Electrical, and Noise Safety

Addresses safe handling of refrigerants, electrical installations, and noise level precautions.

Installation and Operation Procedures

Unit Installation Guidelines

Outlines mechanical, electrical, and safety equipment installation steps according to codes.

Unit Description and Control System

Describes the unit's main components and its electronic control system.

Start-up and Operation Procedures

Details initial, normal start-up, and operation procedures, including stopping and storage.

Troubleshooting and Maintenance

Troubleshooting Common Issues

Covers common problems and solutions for refrigeration plants and compressor units.

Maintenance Schedule and Intervals

Lists daily, periodic, and interval-based maintenance tasks based on operating hours.

Oil Management and Charging

Details oil types, checks, changes, and charging procedures for the compressor unit.

Final Disposal and Compliance

Waste Disposal and Dismantling Safety

Provides safety precautions for dismantling and waste disposal guidelines for unit components.

Declaration of Conformity

States manufacturer's conformity with relevant EU directives and standards.

Johnson Controls SABROE SAB 151 E Specifications

General IconGeneral
TypeScrew Compressor
ModelSAB 151 E
ManufacturerJohnson Controls
BrandSABROE
Frequency50/60 Hz
Sound Pressure Level72 dB(A)
Displacement151 m³/h
Voltage380-480 V
RefrigerantR134a, R404A, R507