APPLICATION GUIDE
OVERVIEW
The Simplicity
®
LINC Gateway operates as a Modbus® Client
providing an interface between a BACnet® MS/TP control system
and devices that communicate using the Modbus RTU protocol.
The Simplicity
®
LINC allows monitoring and control by a third-party
BACnet Building Automation System (BAS).
The Simplicity
®
LINC is preconfigured to provide an interface to UP
products equipped with Simplicity
®
controllers manufactured after
4/2/2008 as well as prior Simplicity
®
Elite™ and Simplicity
®
with
Intelli-Comfort™ controllers.
The Simplicity
®
LINC mounts inside the control panel of the UP
unit and utilizes 24 VAC power from the unit’s control transformer.
One port is connected to the UP controller. The other port must be
connected to the BACnet MS/TP network.
The Simplicity
®
LINC Gateway is preconfigured to obtain
operational data points from the controller and expose them on a
BACnet MS/TP network.
NOTE: Not all Simplicity
®
operating parameters are controlled/
monitored by the Simplicity
®
LINC.
FIGURE 1: WIRE CONNECTIONS
24 — must be grounded
close to the Simplicity LINC
®
The shield must be
connected to ground at
each device.
R
C
24V power is polarity sensitive, incorrect
wiring could result in board damage.
Simplicity
®
LINC GATEWAY
ConFig v1.01d
Question and Answer IconNeed help?

Do you have a question about the Johnson Controls Simplicity LINC and is the answer not in the manual?

Johnson Controls Simplicity LINC Specifications

General IconGeneral
BrandJohnson Controls
ModelSimplicity LINC
CategoryGateway
LanguageEnglish

Summary

Overview of Simplicity®LINC Gateway

Simplicity®LINC Gateway Operation

Operates as Modbus Client, interfaces with BACnet MS/TP systems.

Simplicity®LINC Compatibility

Preconfigured for UP products with Simplicity controllers post-4/2/2008.

Simplicity®LINC Physical Setup

Mounts inside control panel, uses 24 VAC, connects to controller and BACnet network.

Simplicity®LINC Parameter Scope

Not all Simplicity operating parameters are controlled/monitored by the LINC.

Simplicity®LINC Connection and Configuration

Port Identification and BACnet Network

Two ports (BACnet/Modbus), BACnet network wiring, and shielding rules.

MAC Address and Baud Rate Setup

DIP switches for MAC Address (1-99) and BACnet transfer speed.

Device Instance and Naming

Device Instance (DE) Modifier (default 230) and Unit Name (YORK_RTU).

Simplicity®LINC Communication and Software Setup

Modbus Interface and Board Address

Modbus RTU on RS485, and Simplicity® board address (must be 1).

PC Software Configuration and Gateway Setup

PC software for configuration and preconfigured LINC Gateway status.

Flash Memory Write Best Practices

Avoid frequent writes to flash memory to prevent premature failure.

Data Visibility Caveat

Newly updated data may take up to two minutes to be visible.

Simplicity®LINC Troubleshooting and Specifications

Simplicity®LINC LED Troubleshooting

Explains LED indicators for PWR, SYS ERROR, COMM ERROR, Config ERROR, Node Offline, RX, TX, RUN.

Simplicity®LINC General Specifications

Covers power source, frequency, consumption, operating environment, size, and weight.

Simplicity®LINC Hardware Details

Details Port 1/2 types, speeds, connectors, LAN cable, LEDs, and switch selections.

Related product manuals