T9800 series BACnet MS/TP Networked Thermostat Controller Technical Bulletin
Rev 1.4
8 | P a g e
Occupied
FAN-DB
OFF
Low
MV-1308
App:0~5
ALWAYS
ALWAYS
UNOCC-FAN
OFF
Low
MV-1309
App:0~5
ALWAYS
ALWAYS
PWR-F-RSTT
OFF
ON
Recovery
MV-1310
ALWAYS
ALWAYS
ALWAYS
HTG-STG
One Heating Stage -
Fan Coil.
One Heating Stage -
Floor Heating;
Two heating stage;
MV-1311
App:3
App:12,16
NONE
ERROR
OK = No Faults;
E1 = Internal
Sensor Shorted;
E2 = Internal
Sensor Opened;
HI = High
Temperature;
LO = Low
Temperature;
E3 = Remote
Sensor Shorted;
E4 = Remote
Sensor Opened;
E5 = Dew Point
Risk;
E6 = Filter Alarm;
E7 = BI warning.
MV-1312
ALWAYS
ALWAYS
ALWAYS
STATUS
Off;
Cooling;
Heating;
Ventilating;
Idle;
Frost Protecting;
Warning
MV-1313
ALWAYS
ALWAYS
ALWAYS
UNIT-EN
Shutdown;
Enable
MV-1314
ALWAYS
ALWAYS
ALWAYS
TIO2ESP-CTL
Automatic
Manual
MV-1315
App:4
App:13
NONE
OCC-OVRD
No Override;
Occupied;
Unoccupied.
MV-1317
ALWAYS
ALWAYS
ALWAYS