FlexSys Thermostat Zone Controller / LCD Touch Screen
TEC - 3620
Model:
©2016 Johnson Controls | The performance specications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specications, consult the local
Johnson Controls ofce. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
© 2016 AirFixture, LLC
26
Installation / Operation Manual
V160919
TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
Control Setup General
Control Mode Auto Auto, Cooling, or Heating
Unit Enable Enable Enable or Shutdown
Fan Mode* Smart Not Used, On, Auto, Smart
* Fan coil units only
Max Setpoint Offset 3 0 to 20 degrees (F or C based on Units
setting under Display Settings menu)
Fan On Delay* 30 seconds 0 to 120 seconds
* Fan coil units only
Fan Off Delay* 30 seconds 0 to 120 seconds
* Fan coil units only
Frost Protection Yes Yes or No
Reset PID Tuning* No Yes or No
Auto PID Tuning Enable Yes Yes or No
Dehumidification Enable* No Yes or No
* Fan coil units with humidity sensor
Aux Mode Not Used Not Used, Occupied NO, Occupied NC,
Occupied Fan NO, Occupied Fan NC, On,
Off
Inputs
BI1 Configuration Disabled Disabled, Occupancy, Occupancy
Override, Remote PIR, Dirty Filter,
Service, Fan Lock, Open Door, Open
Window
BI2 Configuration Disabled Disabled, Occupancy, Occupancy
Override, Remote PIR, Dirty Filter,
Service, Fan Lock, Open Door, Open
Window
Supply Temp Type Analog Sensor Analog Sensor, Heating NC, Cooling NC
* Non four-pipe units only
Supply Temp Sensor* Nickel Nickel, Platinum, A99B, 2.25k ohm
negative temperature coefficient (NTC),
10k ohm NTC, 10k ohm NTC Type 3
* SAT Mode = Analog Sensor,
non four-pipe
Supply Temp Offset* 0 -5 to 5 (F or C based on Units setting
under Display Settings menu
* Analog Sensor
Zone Temp Sensor Nickel Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
Zone Temp Offset 0 -5 to 5 (F or C based on Units setting
under Display Settings menu
Humidity Offset 0% RH -15% to 15% RH
Reset Sensors No Yes or No
Table 6: Menus and Submenus (Part 3 of 7)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values