TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
27
Network Setup FC Comm Mode BACnet/MSTP BACnet/MSTP, N2
BACnet Instance ID* 4 0 to 4,194,302
* BACnet/MSTP communication mode
N2 Device Address* 1 1 to 255
* N2 communication mode
BACnet Device Address* 4 4 to 127
* BACnet/MSTP communication mode
MSTP Baud Rate* Auto Auto, 1200, 9600, 19200, 38400, 76800
* BACnet/MSTP communication mode
BACnet Encoding Type
BACnet/MSTP Communication Mode
ISO 10646
(UCS-2)
ISO 10646 (UCS-2), ANSI X3.4
(US-ASCII)
Equipment Setup General
Unit Type 4-Pipe 2-Pipe, 4-Pipe, VAV
Heating/Cooling Device Type* Floating On/Off, Floating
* Fan coil units only
Actuator Stroke Time* 30 seconds 5 to 300
* Floating Heating/Cooling device type
only
Cooling Min On Time* 120 seconds 0 to 360 seconds
* Fan coil on/off units only
Cooling MIn Off Time* 120 seconds 0 to 360 seconds
* Fan coil on/off units only
Heating Min On Time* 120 seconds 0 to 360 seconds
* Fan coil on/off units only
Heating Min Off Time 120 seconds 0 to 360 seconds
* Fan coil on/off units only
Table 6: Menus and Submenus (Part 4 of 7)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values