TEC3000 Series On/Off or Floating Fan Coil and Zoning Thermostat Controllers with Dehumidification
Capability Installation Instructions
28
Equipment
Setup (Cont.)
Supply Fan*
Supply Fan Type* Single Speed Single Speed, Multi-speed, Variable
Speed
* Fan coil units only
Start Voltage* 2 VDC 0 to 10 VDC
* Fan coil units only, variable speed fan
Full Speed Voltage* 10 VDC 0 to 10 VDC, proportional
*Fan coil units only, variable speed fan
Min Command* 20% 0 to 100%
* Fan coil units only, variable speed fan
Med Fan Speed On Cmd* 33% 0 to 100%
* Fan coil units only, multi-speed fan
High Fan Speed On Cmd* 66% 0 to 100%
* Fan coil units only, multi-speed fan
Reheat*
Reheat Installed False True or False. When set to True, the Aux
Output is used for Reheat Output.
Reheat Min Damper Position* 20% 0 to 100%
* VAV units with reheat installed
Reheat Fan Required* No Yes or No
*Fan coil units with reheat installed
Reheat Min On Time* 180 seconds 0 to 360 second
* Reheat installed
Reheat Min Off Time* 180 seconds 0 to 360 seconds
* Reheat installed
Changeover
Changeover Mode Auto Auto, Cooling, or Heating
* Non 4-Pipe units
Supply Temp Type Analog Sensor Analog Sensor, Heating NC, Cooling NC
* Changeover Mode = Auto
Changeover Setpoint 55°F 40 to 200°F (4 to 93°C)
* Supply temp type = analog sensor
Supply Temp Sensor Nickel Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
* Supply temp type = analog sensor
Supply Temp Offset 0°F -5 to 5°F (-3 to 3°C)
* Supply temp type = analog sensor
Table 6: Menus and Submenus (Part 5 of 7)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values