TEC3000 Series On/Off or Floating Fan
Coil Thermostats Installation Guide
Applications
The networked TEC3000 Series Thermostat Controllers are stand-alone and field-selectable
BACnet
®
MS/TP or N2 networked devices. Wireless networked models of the TEC3000 Series
Thermostat Controller are also available. On/Off or Floating Fan Coil and Individual Zone
Thermostat Controllers provide control of the following:
Local hydronic reheat valves
Pressure-dependent variable air volume (VAV) equipment with or without local reheat
Two- or four-pipe fan coils
Cabinet unit heaters
Other individual zone equipment using an on/off or floating control input
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/
TP or N2 communication capability that enables remote monitoring and programming for efficient
space temperature control. The wireless models are compatible with the WNC1800/ZFR182x Pro
Series Wireless Field Bus System that enables communication with a building automation system
(BAS). All models include a USB port configuration that reduces installation time by allowing
simple backup and restore features from a USB drive, which enables rapid cloning of configuration
between like units.
Some models feature built-in occupancy sensing capability. These thermostat controllers maximize
up to 30% energy savings in high-energy usage commercial buildings, such as schools and hotels,
during occupied times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and
operation quick and easy. Multiple fan configurations are supported for fan coil equipment types,
as follows:
Single-speed
Multi-speed (two or three discrete speeds)
Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan
coil units with or without reheat. When no heating is required, the thermostat controller monitors
space humidity and activates dehumidification control as necessary. Heat and/or reheat is used as
required to maintain the space temperature. For optimal dehumidification performance, use a fan
coil unit that has a multi-speed or variable-speed fan (VSF).
Important: The TEC3000 Series Thermostat Controller is intended to provide an input to
equipment under normal operating conditions. Where failure or malfunction of the thermostat
controller could lead to personal injury or property damage to the controlled equipment or
other property, additional precautions must be designed into the control system. Incorporate
and maintain other devices, such as supervisory or alarm systems or safety or limit controls,
intended to warn of or protect against failure or malfunction of the thermostat controller.
TEC3012-1x-xxx, TEC3013-1x-xxx, TEC3310-1x-xxx,
TEC3313-1x-xxx, TEC3612-1x-xxx, TEC3613-1x-xxx
LIT-12013161
2019-08-20

Other manuals for Johnson Controls TEC3022

Questions and Answers

  • J
    Jonathan RayAug 28, 2025
    Why is Heating Ineffective on my Johnson Controls Thermostat?
    • R
      Richard ReyesAug 28, 2025
      If your Johnson Controls Thermostat displays 'Heating Ineffective', it means the Supply Air Temperature hasn't increased above the configured Supply Air Temperature Alarm Offset while heating has been active for at least the Supply Air Temperature Alarm Delay. Verify that the heating elements on the rooftop are functioning properly.
  • R
    Randy MataAug 29, 2025
    What does Cooling Ineffective mean on Johnson Controls Thermostat?
    • K
      Kristen ContrerasAug 29, 2025
      If your Johnson Controls Thermostat displays 'Cooling Ineffective', it means the Supply Air Temperature hasn't decreased below the configured Supply Air Temperature Alarm Offset while cooling has been active for at least the Supply Air Temperature Alarm Delay. Verify that the cooling elements on the rooftop are functioning properly.
  • C
    Craig WrightSep 18, 2025
    Why is Heating Ineffective on my Johnson Controls Controller?
    • J
      Julia SampsonSep 18, 2025
      If your Johnson Controls Controller indicates 'Heating Ineffective,' it means the supply air temperature hasn't increased above the configured Supply Air Temperature Alarm Offset, even though heating has been active for at least the Supply Air Temperature Alarm Delay. To resolve this, verify that the heating elements on the rooftop are functioning properly.
  • P
    peter64Sep 15, 2025
    Why does my Johnson Controls TEC3022 say 'Cooling Unavailable due to Control Mode' or 'Heating Unavailable due to Control Mode'?
    • C
      Christy HartSep 15, 2025
      If your Johnson Controls Controller displays 'Idle' with a unit status of 'Cooling Unavailable due to Control Mode' (even when above the cooling setpoint) or 'Heating Unavailable due to Control Mode' (even when below the heating setpoint), it indicates that the control mode setting is incorrect. Here’s what you should do: * If the Control Mode is set to 'Cooling Mode' but the controller is requesting heating, change the Control Mode to 'Auto' or 'Heating'. * If the Control Mode is set to 'Heating Mode' but the controller is requesting cooling, change the Control Mode to 'Auto' or 'Cooling'.
  • C
    Casey LesterSep 12, 2025
    What does 'Partial Restore Complete' mean when restoring settings on my Johnson Controls Fan?
    • J
      Jill HughesSep 12, 2025
      If 'Partial Restore Complete' is displayed when restoring settings on your Johnson Controls Fan, it means not all items in the backup file have been restored. This can happen if a value in the backup file is outside the acceptable minimum or maximum range. To fix this, create a backup file on a USB drive for the TEC that's showing the issue. Edit this backup file on a PC to reflect the desired settings, ensuring the modified values are within the valid range. Finally, restore the settings from this newly edited backup file on the TEC.
  • Z
    zsteeleSep 8, 2025
    What does it mean when my Johnson Controls Fan indicates 'Dirty Filter'?
    • J
      Jennifer WatkinsSep 8, 2025
      If your Johnson Controls Fan indicates 'Dirty Filter', it means equipment connected to the BI configured for a Dirty Filter alarm is triggering the alarm. Replace the filter in the equipment as explained in the manufacturer's instructions.
  • J
    Joan EdwardsAug 30, 2025
    Why does my Johnson Controls Thermostat display Partial Restore Complete?
    • A
      agarciaAug 30, 2025
      If your thermostat displays 'Partial Restore Complete' when restoring from a backup, it means not all items in the backup file were restored. This can happen if a value is outside the acceptable range or if there are inconsistencies in a setting's reliability. To resolve: 1. Create a Backup file on a USB drive for the TEC that is showing the issue. 2. Edit the backup file created in the previous step on a PC to reflect the desired settings. 3. Verify that the modified values are within minimum and maximum range in the backup file. 4. Restore the settings from the newly edited backup file on the TEC.
  • K
    Kathryn SmithAug 30, 2025
    Why is my Johnson Controls Thermostat requesting heating in Cooling Mode?
    • L
      Leslie BarryAug 30, 2025
      Change the Control Mode to Auto or Heating.
  • A
    angelafoleyAug 30, 2025
    Why is Johnson Controls Thermostat requesting cooling in Heating Mode?
    • T
      Taylor RivasAug 31, 2025
      Change the Control Mode to Auto or Cooling.
  • M
    Matthew MathisAug 31, 2025
    What to do if Johnson Controls Thermostat provides an error when trying to upgrade firmware?
    • P
      pgarciaAug 31, 2025
      If your controller shows an error (Error code 1025) when upgrading firmware, it means the firmware on the USB drive is below the minimum required version. Please use firmware version 3.0.2.xxxx (for networked models) or 2.0.2.xxxx (for wireless models) or higher. A reboot is required to clear the Firmware Mismatch fault that occurs.

Summary

Applications

Capabilities and Features

Describes networked/wireless models, occupancy sensing, touchscreen UI, fan configs, and dehumidification.

Installation

Installing the Thermostat Controller

Removing and Mounting the Controller

Steps for removing cover and mounting the base.

Wiring

Terminal Identification and Functions

Describes terminal labels and their functions for various models.

Using the USB Port

Firmware Loading and Backup

Steps for updating firmware and backing up settings.

Settings Restoration and Communication Mode

Procedures for restoring settings and configuring network communication.

Installer Configuration Menu

Screen Reset and Unit Type Selection

How to reset screen and choose between 2-pipe, 4-pipe, or VAV configurations.

Heating;Cooling Type and Fan Configuration

Setting control modes and fan parameters.

VSF, Control Mode, and Fan Mode Settings

Configuring VSF, control modes, and fan operation.

Dehumidification Control

Temperature Setpoints

Configuring Occupancy

PID;PRAC+ Automatic Control Tuning

Resetting and Disabling PID Tuning

Procedures to reset and disable PID tuning parameters.

Available Fault Diagnostics

Troubleshooting

Common Sensor and Temperature Faults

Faults and solutions for zone, supply, and outdoor temperature failures.

Other Faults and Solutions

Faults and solutions for internal sensor, dehumidification, service, and calibration issues.

Faults related to Inputs and Control States

Faults and solutions for open window, fan lock, humidity, and controller errors.

Faults related to Hardware and Firmware

Faults and solutions for touchscreen, board mismatch, firmware, USB, and runtime issues.

Troubleshooting HVAC Operation Faults

Symptoms, causes, and solutions for cooling/heating unavailability and cycling.

Troubleshooting Control and Configuration Errors

Issues with firmware upgrades, temperature response, and unoccupied settings.

Troubleshooting Backup and Restore Errors

Issues with settings backup, restore, and USB access.

Troubleshooting Display and Network Issues

Issues with unresponsive touchscreens, hidden icons, and network connectivity.

Technical Specifications

Johnson Controls TEC3022 Specifications

General IconGeneral
ModelTEC3022
Product TypeTemperature Controller
Supply Voltage24 VAC/VDC
Communication ProtocolBACnet MS/TP
Number of Inputs2
Number of Outputs2
Control AlgorithmPID
DisplayLCD
Enclosure RatingIP20
MountingWall Mount
TypeThermostat
Controller TypeDigital
ApplicationHVAC
Input TypeThermistor
Output TypeRelay
Power Supply24 VAC