TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability Installation Guide
30
5. Select the days to which the schedule should apply. Note that if events are already set for the selected days,
they appear in the corresponding event box. If any events conflict between selected days, an asterisk appears
in the event box. See Figure 18.
6. Select the Occupancy Status icon for the event. See Figure 19.
Figure 18: Selecting the days
Figure 19: Setting the Room Occupancy mode
7. Select the Time Set button. See Figure 20.
8. Set the time to the time at which the event will occur and press Save. The screen resets to the Event Set
Schedule screen.
Figure 20: Selecting the Time Set button (left) and setting the event time (right)
IMPORTANT: Internally, the TEC3000 uses a BACnet schedule where daily schedules are independent of the
previous and next days. The default occupancy of the TEC3000 from the factory is set to Occupied. As a result,
a daily event at 12:00 AM must be scheduled if you do not want the controller to transition to Occupied Mode at
midnight.