TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability Installation Guide
31
9. Press Save to save the completed event or Trash to delete the completed event. See Figure 21. The screen
resets to the Event 1 Set Schedule screen.
Note: If you do not select Save at this point, the event is not saved and you must repeat the event selection
sequence.
Figure 21: Saving the event
10. Select Event 2. See Figure 22. The screen resets to the Event 2 Set Schedule screen. The days are
preselected to match Event 1.
11. Select the Occupancy Status button for Event 2.
Figure 22: Selecting event 2 (left) and setting the occupancy status (right)
12. Select the Time Set button.
13. Set the time for Event 2 and press Save.
14. Press the back arrow
to return to the Scheduling screen.
Overriding the Occupancy mode
The TEC supports a manual override of all other schedule sources (for example, Schedule, Occupancy BI, and
temporary occupancy). To override the Occupancy Mode:
1. Press the Menu icon.
2. Press Scheduling
3. Press Schedule Options.
4. Press Manual Occ Mode and select Occupied, Unoccupied, or No Override.
5. Press
Save and the back arrow to return to the previous screen.
This option is also exposed to the BAS through the point OCCOVRD-MODE.