P5417009-rev.6
3.5 Combinations of Indoor Units and Outdoor Units
Table 3.1 Indoor Unit Model List
Indoor Unit Model
Capacity (MBH)
6 8 12 15 18 24 27 30 36 48 54 60 72 96
Ducted
Ducted (High Static)
(H,Y)IDH_B21S
(H,Y)IDH_B22S
Ducted (Medium Static)
(H,Y)IDM_B21S
(H,Y)IDM_B22S
Ducted (Slim) (H,Y)IDS_B21S
Ducted (EconoFresh) (H,Y)IDM_B21E
Air Handler with DX-Kit (H,Y)MAHP_(B,C,D)21S
Non-
Ducted
Ceiling-Mounted 4-Way Cassette (H,Y)IC4_B21S
Ceiling-Mounted 4-Way Cassette Mini (H,Y)ICM_B21S
Ceiling-Mounted 2-Way Cassette (H,Y)IC2_B21S
Ceiling-Mounted 1-Way Cassette (H,Y)IC1_B21S
Wall-Mounted TIWM_B21S
Ceiling Suspended (H,Y)ICS_B21S
Floor Exposed (H,Y)IFE_B21S
Floor Concealed (H,Y)IFC_B21S
: Available
NOTICE:
For connection to a Ducted (EconoFresh), see below.
Ducted (EconoFresh) only:
Total capacity of Ducted (EconoFresh) is 70%~100% of the outdoor unit capacity.
Ducted (EconoFresh) + Other Standard Indoor Unit:
Total capacity of Ducted (EconoFresh) is 30% or below the outdoor unit capacity.
and
Total capacity of indoor unit, including Ducted (EconoFresh) is 70%~100% of the outdoor unit capacity.