6
The Quality Connection
Selection of Proper Dies
Female Die
Male Die
Applicable Nominal Applicable
Female
Die Male Die
Terminals Size Wire Range
(mm sq.)
8 6.64~10.52
TD-221 TD-211
Non-insulated 14 10.52~16.78 TD-222 TD-211
Terminals and 22 16.78~26.66 TD-223 TD-212
Splices 38 26.66~42.42 TD-224 TD-212
(Butt type, 60 42.42~60.57 TD-225 TD-213
Parallel type) 70 60.57~76.28 TD-226 TD-213
80 76.28~96.3 TD-227 TD-214
100 96.3~117.2 TD-228 TD-214
150 117.2~152.05 TD-229 TD-215
Note: Applicable wire range for parallel type non-insulated slices denotes the
total cross sectional areas of the wires to be used.
1. Choose the correct terminal and wire combination.
2. Choose the correct male and female dies from the chart above to match the nominal size
terminal to be used. The dies are clearly marked with the die number.
CAUTION: SELECTING THE WRONG COMBINATION OF DIES COULD DAMAGE THE
DIES OR THE TOOL ITSELF.