Example for mixed operation with pulse inserts and illuminated push-buttons: 6 x
pulse insert: 6 x 2.8 mA = 16.8 mA current available for lighting elements: 40 mA -
16.8 mA = 23.2 mA Number of lighting elements for 0.9 mA per element: 23.2 mA /
0.9 mA = 25.7 This allows 25 illuminated push-buttons to be connected.
The number of push-buttons is not limited.
Image4: Clampable conductor cross-section for automatic RMD
Image5: Clampable conductor cross-section for pulse insert
Note clampable conductor cross-sections automatic RMD (see figure 4) and
pulse insert (see figure 5).
Mount automatic RMD (4) on DIN rail.
Connect automatic RMD (4), pulse insert (5) and push-button (6) according to
connection diagram (Figure 2) or (Figure 3).
Fit pulse insert or push-button in an appliance box, pulse insert terminals must
be at the bottom.
Install the cover frame and the cover.
If multiple circuit breakers supply dangerous voltages to the device or load,
couple the circuit breakers or label them with a warning so that disconnection
from the supply voltage is ensured.
Set run-on time and operating mode on automatic RMD, see "Operation".
Adjust the brightness threshold and sensitivity on the motion detector cover,
see instructions for the respective cover.
When in combination with a pulse insert, not all functions on the motion de-
tector can be used.
5 Technical data
Power unit for rail mounting, art. no.
1208REG
Power unit for rail mounting, Pulse insert
7 / 10
82599523 15.08.2022
J0082599523