2 Safety
DANGER
Lethal voltages are still present in the connections and cables of the device even after the device
has been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
1. Comply with all safety regulations and current technical connection specifications of the responsible power
supply company.
2. The device is only permitted to be opened or serviced by a qualified electrician.
3. Switch off the grid voltage by turning off the external circuit breakers.
4. Do not touch the cables and/or terminals/busbars when switching the device on and off.
5. Keep the device closed when in operation.
The electrician is responsible for observing all existing standards and regulations. The following applies:
Keep unauthorised persons away from the device and/or system.
In particular, making sure that the locally applicable version of the standard
1
"Requirements for special installations
or locations – solar photovoltaic (PV) power supply systems" is observed.
Ensure operational safety by providing proper grounding, conductor dimensioning and appropriate protection against
short circuiting.
Observe the safety instructions on the product and in this manual.
Switch off all voltage sources and secure them against being inadvertently switched back on before performing visual
inspections and maintenance.
When taking measurements on the live device:
Do not touch the electrical connections
Remove all jewellery from wrists and fingers
Ensure that the testing equipment is in safe operating condition.
Modifications to the surroundings of the device must comply with the applicable national and local standards.
When working on the PV generator, in addition to disconnecting this from the grid it is also necessary to switch off
the DC voltage using the DC isolator switch on the device.
2.1 Intended use
The device is a transformerless PV inverter which converts the direct current of the PV generator into grid-compatible
three-phase alternating current and then feeds the three-phase alternating current into the public power grid.
The device is built using state-of-the-art technology and in accordance with the recognized safety rules. Nevertheless, im-
proper use may cause lethal hazards for the operator or third parties, or may result in damage to the product and other
property.
The device is intended for indoor and outdoor applications and may only be used in countries for which it has been ap-
proved or for which it has been released by KACO new energy and the grid operator.
2
Operate the device only with a permanent connection to the public power grid. The country and grid type selection must
be commensurate with the respective location and grid type.
The requirements of the grid operator must be met for grid connection to take place. The permission of the relevant au-
thorities may also be required in order to secure authorisation to connect to the grid.
1
Country Standard
EU Harmonised document - HD 60364-7-712 (European
implementation of the IEC standard)
USA PV section of NEC 690 and sections in article 100,
690.4, 690.6 and 705.10
Tab.1: Examples of standards specific to business premises
2
WARNING!The device is not intended for use in residential areas and cannot ensure adequate protection of
radio reception in such environments.
Manual Safety | 2
KACO blueplanet 100 NX3 KACO blueplanet 125 NX3 Page 7