LS30 CONTROLLER INSTALLATION AND OPERATING GUIDE
27
These values can only be adjusted in same values as '0' only
when the operaon of relays are not desired.
6.2 Mulfuncon Dedecon
'Open' inscripon
appears on screen,
You can solve the problem according to
'6.1.1 Open Mulfuncon Code'. If you
can not solve go to 6.4.
'err' inscripon on
screen,
You can solve the problem according to
'6.1.2 err Mulfuncon Code'. If you can
not solve go to 6.4.
No display on
screen when ener-
gized,
Make sure that supply voltage is reached
properly to LS30 Controller. If the energy
is reached properly the LS30 Controller
can be defecve. Go to 6.4.
Relays do not oper-
ate even if we have
entered relay on o
values,
Cut the energy of LS30 Controller. Aer-
wards remove the lower terminal from
its place that relay that energy connec-
on is made and that relay outputs are
connected. Take measurements from
terminals 20&19, 17&16, 14&13 at
Ω scale of measurement device. At all
measurements you should read short
circuit (resistance values close to zero).
Relay that zero vales are not read can be
defecve, go to 6.4.
Although the level
quanty is dierent
connuous '100'
value appear at
upper display,
Replace the connecons of 1 and 2 ter-
minals of LS30 Controller. If you can not
solve problem make sensor defect de-
terminaon as per 6.3.