LS30 CONTROLLER INSTALLATION AND OPERATING GUIDE
26
6. MULFUNCTION
In trouble shoong make sure that the oats of LS30 and MLG30
(whichever is being used with LS30 Controller) Level Control
Equipments are operang accurately. The wrongly selected, that
does not oat or defecve oats prevent you to take measure-
ment (see assembly and user guide for MLG series level control
equipments).
6.1 General Mulfuncon Codes
6.1.1 'Open' Mulfuncon Code
At errors related with sensor or sensor reference that can be
detected by device the 'Open' failure code ashes at the up-
per display. This may come to the meaning that the sensor
connecons are not made correctly or brokerage at cables.
6.1.2 'err' Mulfuncon Code
In case of adjustment of relay parameters at equal values 'err'
failure code appears in lower display. The relay on and o val-
ues should be denitely adjusted at dierent values.
Primarily make sure that sensor connecons are made as
per 3.3.1 or 3.3.2 in sequence,
If you are sure that the connecons are made as per se-
quence make sure that your cable is not broken,
If you are sure that cable is not broken make sure that the
reference values are adjusted accurately according to ad-
justment of '5. Adjustement of Sensor Reference Values',