EasyManuals Logo

KEB COMBIVERT F4-F Quick Reference

KEB COMBIVERT F4-F
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
GB-15
Start-Up Instructions
In case of error message „E.OL2“ adjust LF.38=0 (8 kHz operating
frequency).
In case of wrong travel direction (up and down exchanged) activate
the reversal of driving direction with LF.05=1.
The driving comfort can be optimized with the following parameters:
LF.50 Starting jerk in m/s
3
LF.51 Acceleration in m/s
3
LF.52 Deceleration jerk in m/s
3
LF.53 Deceleration in m/s
3
LF.54 Stopping jerk in m/s
3
The ramps become steeper by increasing the values, e.g. the jerk
value becames harder.
If the cabine rolls back when releasing the brake, increase LF.33 in
steps of 500.
If the lift at the beginning of the drive runs against the brake, increase
LF.70 (brake release time) because the brake release is not fast
enough.
The brake engage time can be increased with parameter LF.79, if the
brake is not closed after stopping when the inverter switches off the
modulation.
Optimization

Other manuals for KEB COMBIVERT F4-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F4-F and is the answer not in the manual?

KEB COMBIVERT F4-F Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F4-F
CategoryLifting Systems
LanguageEnglish