8. Locations to Avoid
(See Figures 7-A, 7-B, & 7-C for recommended locations)
In the garage. Products of combustion are present when you start your automobile.
Normal cooking may cause nuisance alarms. If a kitchen alarm is desired, it should have an alarm silence
feature or be a photoelectric type.
Do not install within 1.8m (6 ft). of heating or cooking appliances.
In an area where the temperature may fall below 4.4 ºC (40 ºF) or rise above 37.8 ºC (100ºF), such as garages
and unfinished attics.
In dusty areas. Dust particles may cause nuisance alarms or a failure to alarm.
In very humid areas (above 95% RH, non-condensing), as moisture or steam can cause nuisance alarms..
In insect-infested areas.
Smoke alarms should not be installed within 0.9m (3 ft) of the door to a bathroom containing a tub or
shower, forced air supply ducts used for heating or cooling, ceiling or whole house ventilating fans, or other
high air flow areas.
Near lights. Electronic “noise” generated by the electronics may cause nuisance alarms.
Do not install near vents, flues or chimneys.
Do not install near fans, doors, windows or areas directly exposed to the weather.
Avoid installing where the unit will be exposed to direct sunlight.