Architectural and Engineering
Specifications
The strobe light shall be Kidde Unit SL177i or approved
equal. It shall be powered by a 120VAC, 60Hz source. The
temperature operation range shall be between 40°F and
100°F (4°C and 38°C). The strobe light can be installed on
any standard single gang electrical box, up to a 4” octagon
junction box. The electrical connection (to the device) shall
be made with a plug-in connector. A maximum of 24 Kidde
devices can be interconnected in a multiple station arrange-
ment. The interconnect system must not exceed the
NFPA (National Fire Protection Association) limit of 18
initiating devices (Smoke, heat, CO, etc) interconnected,
it is still possible to interconnect 6 strobe lights and or
relay modules.
The device shall provide optional tamper resistance that
deters removal of the unit from the wall or ceiling.
This unit shall include a bright candela strobe light with
a flash rate of one (1) flash per second. This unit shall be
interconnected with Kidde smoke alarms, heat detectors
and/or carbon monoxide alarms. The unit shall at a minimum
meet the requirements of UL217, NFPA72, (chapter 10 & 11
2002 edition) The State of California Fire Marshall, NFPA101
(One and two family dwellings, Federal Housing Authority
(FHA), Housing and Urban Development (HUD), Americans
with Disabilities Act (ADA).
Installation of Strobe Light
The strobe light should be installed to comply with all local
codes having jurisdiction in your area, Article 760 of the
National Electric Code, and NFPA 72. Make certain all devices
are wired to a single, continuous (non-switched) power
line, which is not protected by a ground fault interrupter. A
maximum of 1000 ft. of wire can be used in the interconnect
system. Light output gradually decreases as viewing angle is
increased. Consult chart in users guide to determine the best
location for the strobe light installation.
120VAC Dual Mode Strobe Light
for the Hearing Impaired
Model Number SL177i
Technical Specifications
Model: SL177i
UPC: 0-25417-19129-5
Power Source: 120VAC, 60HZ
Electrical Rating: 100 - 130 VAC, 60HZ, 80 mA
standby, 44 mA inrush, 1.5 A peak,
390 mA when operating.
Temperature Range: 40˚F to 100˚F (4˚C to 38˚C)
Flash Rate: 1 flash per second
Light Output 177 Candela
Size: 5.6” in diameter x 3” depth
Weight: 1lb
Interconnects: Up to 24 Kidde devices of which 18
can be initiating devices.
Warranty: 5 year limited warranty
Ordering Information
Gift Box UPC: 0-25417-19129-5
Part Dimensions Case/ Layers/ Skid
Number I 2 of 5 Pack Quantity (w x d x h inches) Weight Skid Skid Weight
SL177i* N/A Individual 5.75 x 3.25 x 6.75 1lb N/A N/A N/A
SL177i 200 25417 19129 9 3 units 6.5 x 10.5 x 6.5 3lbs 120 5 360lbs
* Not for sale by individual unit
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-SL177i sheet rev. 01-2009

Other manuals for Kidde SL177i

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde SL177i and is the answer not in the manual?

Kidde SL177i Specifications

General IconGeneral
BrandKidde
ModelSL177i
CategoryCarbon Monoxide Alarm
LanguageEnglish

Related product manuals