2.APPLICATIONS
PRIMARY DIRECT Locate the strobe light on the ceiling in the center of the room
AND INDIRECT or on the wall a minimum of 80"(2 m) above the floor.
VISIBLE SIGNAL For rooms larger than 250 sq. ft. (14 ft by 16 ft - 4.27m by
4.88 m) the notification device should be located within 16ft
(4.88m) of the pillow.
SUPPLEMENTARY The strobe may be located less than 80" (2 m) above the floor.
VISIBLE SIGNAL
3.RECOMMENDED LOCATIONS OF VISUAL SIGNALING
DEVICES
Locate the first strobe light in the bedroom in which the hearing impaired individual sleeps. If the
bedroom door is kept closed at night, an interconnecting smoke detector must also be installed in
that bedroom.
Locate additional strobe lights in any lived-in room where a hearing impaired individual would need
to be notified of an alarm condition.
4.LOCATIONS TO AVOID
¥ In direct sunlight or high ambient light areas ( The bright light may reduce ones ability to notice the
strobe light)
In areas where the temperature may fall below 32
o
F or rise above 100
o
F
In areas with high humidity
Avoid outdoor locations (This device is not listed for outdoor use).
5.INSTALLATION INSTRUCTIONS
"READ CAREFULLY" WIRING REQUIREMENTS:
This Strobe Light should be installed on a U.L. listed Junction box. All connections should be made
by a Qualified electrician and must conform to Article 760 of the U.S. National Electrical Code, NFPA
72, Underwriters Laboratories standards 217 and 1971 and / or any other codes having jurisdiction
in your area. If this strobe light is being installed to comply with The Americans for disabilities Act
refer to that act for any applicable requirements.
he appropriate power source is 110-130 Volts A.C. single phase supplied from a non-switched cir-
cuit, which is not protected by a ground fault interrupter.
MODEL SL177I WIRING INSTRUCTIONS: For A.C. QUICK CONNECT 3 WIRE HARNESS.
CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING THE STROBE
LIGHT.
1. When Strobe lights and alarms are interconnected, all the interconnected devices must be powered
from the same circuit.