Chapter 7: Service and troubleshooting
130 P/N 3101890-EN • REV 006 • ISS 21JUN18
Table 46: VM-NOCF troubleshooting
Possible causes
LED not flashing on
• The ribbon cable between the adapter card and the electronics card is
improperly installed or defective
• The adapter card is not properly seated in J6 on the CPU
LED not flashing on
• An incorrect cable is connected to the port
• A fiber strand may be broken or missing
• Lack of continuity between one panel and another
LED steady on transceiver Jumper JP1 was left in the test position
Te
st jumpers
Jumper J2 on the electronics card is used to put the module in test mode. See the VM-NOCF Fiber Network
Option Module Installation Sheet (P/N 3101783-EN) for testing instructions.
D12LS-VM control-indicating modules troubleshooting
The D12LS-VM control-indicating modules operate independently of the option card on which they are installed.
However, they use the option card’s electronics to communicate with the VM-CPU.
The lamp test function will quickly isolate hardware problems from programming problems with any control-
indicating module. See “Performing a lamp test” on page 46.
Table 47: Control-indicating module troubleshooting
Possible cause
LEDs, buttons, and host option
• There is no power to the panel
• The ribbon cable between the control-indicating module and the CPU
or connected control-indicating module is loose or defective
• The control-indicating module is defective
LEDs and buttons are
, but the host option card
• The ribbon cable between the control-indicating module and the CPU
or connected control-indicating module is loose or defective
• The control-indicating module is not defined in the VM-CU
• The control-indicating module is defective
LEDs respond incorrectly • The control-indicating module is not defined in the VM-CU
• The LED is not identified correctly in the VM-CU
• A correlation governing LED operation is not correctly written
utton does not perform the
• The control-indicating module is not defined in the VM-CU
• The button is not identified correctly in the VM-CU
• A correlation governing button operation is not correctly written