Chapter 2: Product description
P/N 3101890-EN • REV 006 • ISS 21JUN18 21
Enable Menu
All components are enabled at power-up unless programmed otherwise. Use the commands on the Enable Menu
to place parts of the system that have been disabled back into service.
Table 10: Enable Menu selection descriptions
Selection
Access level Description
Device
2 Enables a device or circuit; requires the panel, card, and device address
Card
4 Enables an option card or control-indicating module; r
equires the panel and
card address
Group
Level 3: AND,
Zone, and Inst.
Text groups
Level 4: Service
Group
Displays the Enable Group Menu from which you can enable the following:
AND Group: Select from a list of AND groups
Service Group: Select from a list of Service groups
Zone Group: Select from a list of Zone groups
Inst Text Group: Select from a list of Instruction Text groups
Time Control
3 Displays a list of the programmed time controls from which a time control
may be enabled.
Switch
3 Enables a switch on a control-indicating module; requires the panel, card,
and device address
LED
3 Enables the LEDs on a control-indicating module; requires the panel, card,
and device address
Disable Menu
Use the commands on the Disable Menu to take individual zones, input and output points, option cards, and other
parts of the fire alarm system out of service.
Table 11: Disable Menu selection descriptions
Selection
Access level Description
Device
2 Disables a device or circuit; requires the panel, card, and device address
Card
4 Disables an option card or control-indicating module; requires the panel
and card address
Group
Level 3: AND,
Zone, and Inst.
Text groups
Level 4: Service
Group
Displays the Disable Group Menu
from which you can disable the following:
AND Group: Select from a list of AND groups
Service Group: Select from a list of Service groups
Zone Group: Select from a list of Zone groups
Inst Text Group: Select from a list of Instruction Text groups
Time Control
3 Displays a list of the programmed time controls, from which a time control
may be disabled
Switch
3 Disables a switch on a control-indicating module; requires the panel, card,
and device address
LED
3 Disables the LEDs on a control-indicating module; requires the
panel, card,
and device address