Chapter 2: Product description
P/N 3101890-EN • REV 006 • ISS 21JUN18 23
Selection
Access level Description
Slow Blink: Select one of the states from the Output Priority Menu
(see
the priority states described in “Steady” above)
Set
Latch
Low Priority
Medium Priority
High Priority
Audio Amp [1]
3 Changes the output state of an ACHS channel selector card. Select one of
the states from the Output Priority Menu. Requires a panel, card, and
device address.
Set: Overrides low, medium, and high priority instructions and forces
the device to the desired state. The Set priority does not reset the
device’s priority counters.
Latch
: Overrides low, medium, and high priority instructions and forces
the device to the desired state. The Latch priority does reset the
device’s priority counters.
Low Priority: Forces the device to the desired state and adjusts the
Low Priority counter accordingly.
Medium Priority: Forces a device to the desired state and adjusts the
Medium Priority counter accordingly.
High Priority: Forces a device to the desired state and adjusts the H
igh
Priority counter accordingly.
Audio Message
[
1]
3 Allows selection of a different audio message and channel for a
corresponding amplifier. Requires the message and channel for a panel,
card, and device address.
Sensor Bypass
2 Keeps the photo element on a PHS Multisensor Smoke Detector from
generating a supervisory message. Requires a panel, card, and device
address).
Gas Accel
Response
2 Accelerates the carbon monoxide (CO) rate of detection for a CO detector
for testing purposes. Requires a panel, card, and device address.
Remote Read
Lock
2
Use when connecting to the panel to read status and diagnostic information
via TCP/IP instead of the RS-232 connection. By default, this feature is
“unlocked.” Locking this feature prevents reading from the panel.
The command can be issued to a single panel or all panels.
Note: Activating and restoring the Remote Read Lock command does not
affect reading panel status and diagnostic information over the RS-232
connection.