configure profile table, and then execute PLS instruction.
Each PTO/PWM generator also provides a status bytes in SM area, user can get the status information of
PTO/PWM generator from the status bytes, as shown in following table.
Q0.0
Q0.0
Q0.0
Q0.0 Q0.1
Q0.1
Q0.1
Q0.1 Q0.4
Q0.4
Q0.4
Q0.4 Q0.
Q0.
Q0.
Q0. 5
5
5
5 Description
Description
Description
Description
SM66.0 SM76.0 SM 9 6.0 SM 10 6.0 Reserved
SM66.1 SM76.1 SM 9 6.1 SM 10 6.1 Reserved
SM66.2 SM76.2 SM 9 6.2 SM 10 6.2 Reserved
SM66.3 SM76.3 SM 9 6.3 SM 10 6.3 PWM idle: 0=No, 1=Yes
SM66.4 SM76.4 SM 9 6.4 SM 10 6.4
Whether the cycle time or pulse number of PTO is
wrong: 0=No, 1=Yes
Note:
Note:
Note:
Note: Cycle
Cycle
Cycle
Cycle time
time
time
time and
and
and
and pulse
pulse
pulse
pulse number
number
number
number must
must
must
must be
be
be
be greater
greater
greater
greater
than
than
than
than 1.
1.
1.
1.
SM66.5 SM76.5 SM 9 6.5 SM 10 6.5
PTO profile terminated due to user command:
0=No, 1=Yes
SM66.6 SM76.6 SM 9 6.6 SM 10 6.6 Reserved
SM66.7 SM76.7 SM 9 6.7 SM 10 6.7 PTO idle: 0=No, 1=Yes
The PTO idle bit or PWM idle bit indicate the completion of the PTO or PWM output .
2.3.3.3
2.3.3.3
2.3.3.3
2.3.3.3 PTO
PTO
PTO
PTO Operations
Operations
Operations
Operations
The fallowing takes PTO0 as an example to introduce how to configure and operate the PTO/PWM generator
in the user program.
There are two procedures for using PTO: Configure related control registers and initialize PTO. Execute PLS
instruction.
Use SM0.1 (the first scan memory bit) to call a subroutine that contains the initialization instructions. Since
SM0.1 is used, the subroutine shall be executed only once, and this reduces CPU scan time and provides a
better program structure.
Execute
Execute
Execute
Execute the
the
the
the PTO
PTO
PTO
PTO (Single-Segment
(Single-Segment
(Single-Segment
(Single-Segment Operation)
Operation)
Operation)
Operation)
1) Set control byte SMB67 according to the desired operation.
For example, SMB67 = B#16#85 indicates:
Enable the PTO/PWM function