KP310V1.0 Controller Operation Manual
- 17 -
13 Preheat delay ○○●●○● 0-100 0.1s 50
Set Output 1 or Set Output 2 is
setted as “ Genset Preheat ”, it
works when genset starts,
controller start to count down..
14 Safety Delay ○○●●●○ 20-255 0.1s 60
Within the safety delay, under oil
pressure, high water temperature,
under speed 、 under voltage 、
under frequency 、 charging fault.
Generator
15
Phase Type
○○●●●● 0-4 1 0
0- 3-Phase 4-Line/3P4L
1- 3-Phase 3-Line/3P3L
2- 1-Phase 2-Line/1P2L
3- Double voltage
4- Double voltage select
16 Current Ratio ○●○○○○ 1-65535 1A/5mA 50 External CT ratio
17
Under
Frequency
○●○○○● 0-800 0.1Hz 450
18 Over Frequency ○●○○●○ 0-800 0.1Hz 550
19 Under Voltage ○●○○●● 0-5000 0.1V 2050
20 Over Voltage ○●○●○○ 0-5000 0.1V 2450
21 Over Current 1 ○●○●○● 0-65535 0.1A 450 Generator pre-overload
22 Over Current 2 ○●○●●○ 0-65535 0.1A 500 Generator overload
23
Under
Frequency Fault
Delay
○●○●●● 0-65535 0.1S 20
Generator output under frequency
Stop Delay
24
Over Frequency
Fault Delay
○●●○○○ 0-65535 0.1S 5
Generator output over frequency
Stop Delay
25
Under Voltage
Fault Delay
○●●○○● 0-65535 0.1S 20
Generator output voltage low Stop
Delay
26
Over Voltage
Fault Delay
○●●○●○ 0-65535 0.1S 5
Generator output voltage high
Stop Delay
27
Over Current 1
Fault Delay
○●●○●● 0-65535 0.1S 600
Genset pre-overload delay timing
28
Over Current 2
Fault Delay
○●●●○○ 0-65535 0.1S 50
Genset overload delay timing
29
Over Current 1
Stop Delay
○●●●○● 0-65535 0.1S 300
Genset pre-overload stop delay
timing
30
Over Current 2
Stop Delay
○●●●●○ 0-65535 0.1S 300
Genset overload stop delay timing
Battery
31 Under Voltage ○●●●●● 0-400 0.1V 100
Battery voltage under voltage
alarm
32 Over Voltage ●○○○○○ 0-400 0.1V 180 Battery voltage over voltage alarm