KP310V1.0 Controller Operation Manual
- 24 -
9. Commission
Before commission, please check as follows
1Check all connections and wires
2Right connection with batteries;
3Right connection of Emergency Stop button with battery
4Take proper measures to prevent engine from starting such as dismantle fuel valve connections,
then connect with battery, select manual mode.
5Press
start button, genset will start ; start failure alarms, press Stop to recover
the controller
6Recover Engine to startsuch as recover fuel valve connections, press
start button ,
genset will start , if everything is OK, genset will be in the idle state for a whileif idle running is
availablethen genset will run normally. In this period, check if everything is OK, for example
voltage, frequency. If there are some abnormal situations, stop genset, check the connection refer
to the Manual
7Please contact with us if you need help..
10. Applications
12
3
4
56
7
8910
11 12
13
14
15 16
17
18
19
21
20
22
23
24
2526
27
28293031
KP310V1.0 GENSET CONTROLLER
ABCN
IA IB ICICOM
DIR
TXD
RXD
Comm_GND
Comm_VCC
B-
B+
EM Stop
+
Fuel
High Temp
Oil Press
Aux_In1
Aux_In2
Remote
120/240 Select
Crank
Start sw
Bat Charge
Preheat
Aux_Out1
Aux_Out2
+
-
MPU
A
B
C
N
U
V
W
N
QF