9. Commission
Before commission, please check as follows:
1、Check all connections and wires;
2、Right connection with batteries;
3、Right connection of Emergency Stop button with battery;
4、Take proper measures to prevent engine from starting such as dismantle fuel valve connections,
then connect with battery, select manual mode.
5、Press
(start )button, genset will start ; start failure alarms, press (Stop )to recover
the controller;
6、Recover Engine to start(such as recover fuel valve connections), press
(start )button ,
genset will start , if everything is OK, genset will be in the idle state for a while(if idle running is
available)then genset will run normally. In this period, check if everything is OK, for example
voltage, frequency. If there are some abnormal situations, stop genset, check the connection refer
to the Manual;
7、Please contact with us if you need help..