KP310V1.0 Controller Operation Manual
- 19 -
3-Genset Start
4-Genset Idle
5-Genset Running
6-Genset Electric Parameters
Normal
7-System Warning Alarm
8-System Delay Stop Alarm
9-System Stop Alarm
10-System Alarm
11-Manual Mode
12-Remote Mode
13-Oil Filter Overtime
14-Fuel Filter Overtime
15-Air Filter Overtime
16-Start Failure
46 Set Output 2 ●○●●●○ 0-16 1 0
0-Reserved
1-Genset Stop
2-Genset Preheat
3-Genset Start
4-Genset Idle
5-Genset Running
6-Genset Electric Parameters
Normal
7-System Warning Alarm
8-System Delay Stop Alarm
9-System Stop Alarm
10-System Alarm
11-Manual Mode
12-Remote Mode
13-Oil Filter Overtime
14-Fuel Filter Overtime
15-Air Filter Overtime
16-Start Failure
Idle
47 Start idle Time ●○●●●● 0-65535 0.1s 0
Timing from start idle running to
rated RPM
48 Stop idle Time ●●○○○○ 0-65535 0.1s 0
Timing from stop idle running to
successfully stop.
Password
49 Password ●●○○○● 0-65535 1 0310 Set Password
Generator Parameter
50
L1 Phase
Voltage Gain
●●○○●○ 0-2047 1 1024
Regulate the Gain to display the
same L1 phase voltage on the
controller with the actual voltage.