Document No.:KE-4010-11 Page: 18/58
(5)Checkiftheoperatingpressurehasbeensetwithyourrequiredspecification.
(6)Checkifanequippedairregulatorhasbeensetforyourrequiredoperationpressure.
(7)Ifaspeedcontrollerisequipped,adjusttheflowrateoftheexhaustairtomatchyourrequiredoperation
speed.
Useeithercompressedinstrumentationairornitrogengasforoperationofactuators.
Useofanyotheroperatingmediummayaffectthefunctionofactuators.
Useofoperationpressureexceeding0.7MPamaydamageactuatorsoraccessories.
Keeptheoperationmediumcompletelydry. Highhumiditycausesrustandmayresult
inmalfunctionorfailureofactuatorsoraccessories.
Apartto avoidenteringwaterinto aspringcase(Mizukiller)is installed on spring
return type actuators breathing port. And The Mizukiller is sealed with a sticker.
Removethestickerbeforerunningautomatedoperation.
(ForproductsshippedbeforeDecember2009,acapisinstalledonspringreturntype
actuators breathing port instead of the Mizukiller. Remove the cap before running
automatedoperation.Ifthecapremains,actuatorspeedmaybecomeslow.)
WhenTypeFASspringreturnactuatorisusedoutsideorinwetcondition, the
Mizukillerhastobeinstalledintoit.IftheMizukillerisnotinstalled,watermayenterinto
aspringunitandcauseamalfunction.
19. ManualOperationofActuators
19.1ManualoperationofFSeriespneumaticvalveactuatorsisavailableforTypeFAdoubleactiondrive,asa
standardfeature. ManualoperationofTypeFASspringreturnactuatorsisoptionallypossibleasprovidedin
Appendixofthismanual.
19.2Manualoperationofde-energizedTypeFAdoubleactionactuators
(1) Iftheactuatorisnotequippedwithaby-passvalveandasolenoidvalve,disassembletheairtubingto
equalizethehousingpressurewiththeatmosphericlevel,androtatetheshaftontopofthehousingwitha
spannerorawrench,tomanuallyoperatetheactuator.
(2) Iftheactuatorisequippedwithaby-passvalvebutwithnosolenoidvalve,setthevalvetothe“manual”
position to equalize the housing pressure with the atmospheric level to manually operate the actuator.
Refertotheinstructionsprovidedontheidentificationplateattachedtotheby-passvalve.
(3) Iftheactuatorisequippedwithasolenoidvalve,butwithnoby-passvalvenor pressureequalizervalve,
followtheinstructionsgiveninItem19.2(1)tomanuallyoperatetheactuator.
(4)Iftheactuatorisequippedwithasolenoidvalveandapressureequalizervalve(CKDModelV1000-08),
rotatetheoperationhandleoftheequalizervalveto90°againsttheflowdirectiontoequalizethehousing
pressuretotheatmosphericlevel. TheactuatorisnowreadyformanualoperationasprovidedinItem
19.2(1). Thisprocedurealsoappliestotheactuatorsbeingenergized.