Document No.:KE-4010-11 Page: 41/58
2. ConversiontoAIR-FAIL-OPENMode
The standard AIR-FAIL-CLOSE mode of KITZ Type FAS spring return actuator can be converted to
AIR-FAIL-OPENmode,withoutchangingitscounter-clockwiseopeningoperation(Fig.1).
(1) Checkthatthehousingpressurehasbeenequalizedtotheatmosphericlevel,loosen4hexagonheaded
boltsanddisassembletheendcover.
(2) Alsodisassemblethespringcartridgeunit.
(3) ForFAS-6,removetherubberplugandputitintotheoppositesideairpath.
(4) Mountthespringcartridgetotheoppositeendopeningofthehousing.
(5) Alsomounttheendovertotheoppositeendopeningofthehousing,inplaceofthespringcartridgeunit.
(6) MoveaportstopperplugfromPort[S]toPort[O].
StandardAIR-FAIL-CLOSEOptionalAIR-FAIL-OPEN
Fig.1
(7) ApplytheactualoperationpressuretoPort[S]anddetectexternalairleakagewithusingsoapsolution,
throughthecontactoftheendcoverwiththehousing,thestopperboltandthesealwasher(Fig.2).
Fig.2
(8) Then,energizetheactuatorfortrialoperationtoensuretrouble-freefunction.
(9) InsertMizukilleronabreathingportofaspringcase.
Endcover/housingcontact
Stopperbolt/sealwasher
Rubberplug
FAS-6
Oppositeside