Document No.:KE-4010-11 Page: 43/58
3. AdjustmentofIntermediateValveOpeningRange
3.1Byuseofanoptionallongerstopperboltasakit,thevalveopeningrangecanbeadjustedwithinarangeof
-7° to97°. Thekitshallbemountedonthelefthandendcoverforadjustmentoftheopeningrange,while
itshallbemountedreverselyfor adjustment oftheclosingrange(Fig.3). Follow theworkinginstructions
providedbelow.
AdjustingopeningrangeAdjustingclosingrange
Fig.3
(1)Equalizethehousingpressurewiththeatmosphericlevel,bymeansofoperationofanequalizervalveor
disassemblyoftheairtubing.
(2)Removeahexagonnut,asealwasherandastopperbolt(ahexagonsocketsetscrew)fromtheendcover
ofeitherside,dependingonhowtomakeadjustment.
(3)Mountanoptionallongstopperboltontheendcover,andtemporarilytightenitwithasealwasheranda
locknutalsobeingprovidedasanoptionalkit.
(4)Rotatethelongstopperboltandadjustthevalveopening(orclosing)range.
(5)TightenthelocknutwiththetorquespecifiedinTable3below:
Table3.Locknuttighteningtorque
Actuator Locknuttighteningtorque
FA/FAS-1 3 to 5N・m
FA/FAS-2 5 to 8N・m
FA/FAS-3 9 to 15N・m
FA/FAS-4 25 to 30N・m
FA/FAS-5 40 to 50N・m
FA/FAS-6 100 to 120N・m
(6)PutanO-ringoverthestopperboltandtightenacaponthelocknutsecurely.
(7)ApplytheactualoperationpressuretobothPort[O]andPort[S],anddetectairleakagewithsoapsolution,
throughtheadjustmentkitparts. Wipeoffthesoapsolutionafterwards.
Sealwashe
O-ring
Long stopper bolt
Lock nut
Cap