51
Designation Exchange in
case of
Defect
Exchange regularly Interval
HD - Pump YES -
Gear oil - YES 1.) 200 h
2.) 2500h
Valve kit for HP - pump YES YES 4.000 h
Gasket set for HP - pump YES YES 4.000 h
Tension pulley YES After visual and mech. check
At the discretion of the technician
Toothed belt YES After visual and mech. check
At the discretion of the technician
High pressure switch 150 bar YES For safety reasons
Exchange every 2 years
Low pressure switch 1.6/2 bar YES For safety reasons
Exchange every 2 years
2/2 way solenoid valve NC 230V 1/2" 0-6 bar YES -
2/2 way HP solenoid valve V2A; 0-200 bar YES -
Low pressure gauge YES -
High pressure gauge YES -
Gasket set for nozzle block YES -
High pressure nozzle YES Change or clean when spray picture
decreases
PE filter for high pressure nozzle YES Change 2 x yearly
Filter element (make Brauckmann F76 (S)
100µm)
YES -
HD hose 3 m length YES according to VDI 20066 replacement
every 5 years
5 years
HD hose 0.262 m 2 x 90° S-shape YES according to VDI 20066 replacement
every 5 years
5 years
Engine YES -
1.) First oil change
2.) Regular oil change
Maintenance schedule- CERTO high pressure humidifier