STE-6000 Series Room Temperature Sensors 11 Applications Guide
Setpoint Variable (STE-6012/14/16/17/18/19/20 only)
1. In the BACstage soware main menu, select
Objects > Analog Values.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Click in the Units column and select °F
(Fahrenheit) or °C (Celsius).
5. Click End Edit.
6. Click Yes for “Send Update Notication Now?”
7. Click OK.
Override Input (STE-6012/13/15/16/17/18/19/20 only)
1. In the BACstage soware main menu, select
Objects > Binary Values.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Click in the Units column and select O/On (or
No/Yes, Stop/Start, Disabled/Enabled, Inactive/Active
according to preference).
5. Click End Edit.
6. Click Yes for “Send Update Notication Now?”
7. Click OK.
Supply Output (STE-6012/6016 only)
NOTE: The STE-6012/6016 is powered from the
controller output. A supply of 7.5 volts DC
puts the sensor in setback/setup mode and
12 volts puts it in normal/override mode.
1. In the BACstage soware main menu, select
Objects > Outputs.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Select Object Type: Analog if it is not the default.
5. Select Device Type: Volts 0–10.
NOTE: This only sets the scale; the actual voltage
may go up to 12 volts DC.
6. Click End Edit.
7. Click Yes for “Send Update Notication Now?”
8. Click OK.
NOTE: In the Adobe Acrobat le of this
document, you can select the table below
to copy and paste the 128 lines into the
appropriate device table section of the
BACstage *.BAC panel le.
X1=54.0
X2=54.3
X3=54.6
X4=54.9
X5=55.2
X6=55.5
X7=55.8
X8=56.1
X9=56.4
X10=56.7
X11=57.1
X12=57.4
X13=57.7
X14=58.1
X15=58.4
X16=58.8
X17=59.1
X18=59.5
X19=59.9
X20=60.3
X21=60.7
X22=61.1
X23=61.5
X24=61.9
X25=62.3
X26=62.7
X27=63.2
X28=63.6
X29=64.1
X30=64.5
X31=65.0
X32=65.5
X33=66.0
X34=66.5
X35=67.0
X36=67.5
X37=68.1
X38=68.6
X39=69.2
X40=69.8
X41=70.4
X42=71.0
X43=71.6
X44=72.2
X45=72.9
X46=73.5
X47=74.2
X48=74.9
X49=75.6
X50=76.3
X51=77.1
X52=77.8
X53=78.6
X54=79.4
X55=80.3
X56=81.1
X57=82.0
X58=82.9
X59=83.8
X60=84.8
X61=85.8
X62=86.8
X63=87.8
X64=88.9
X65=90.0
X66=90.0
X67=90.0
X68=90.0
X69=90.0
X70=90.0
X71=90.0
X72=90.0
X73=90.0
X74=90.0
X75=90.0
X76=90.0
X77=90.0
X78=90.0
X79=90.0
X80=90.0
X81=90.0
X82=90.0
X83=90.0
X84=90.0
X85=90.0
X86=90.0
X87=90.0
X88=90.0
X89=90.0
X90=90.0
X91=90.0
X92=90.0
X93=90.0
X94=90.0
X95=90.0
X96=90.0
X97=90.0
X98=90.0
X99=90.0
X100=90.0
X101=90.0
X102=90.0
X103=90.0
X104=90.0
X105=90.0
X106=90.0
X107=90.0
X108=90.0
X109=90.0
X110=90.0
X111=90.0
X112=90.0
X113=90.0
X114=90.0
X115=90.0
X116=90.0
X117=90.0
X118=90.0
X119=90.0
X120=90.0
X121=90.0
X122=90.0
X123=90.0
X124=90.0
X125=90.0
X126=90.0
X127=90.0
X128=90.0