STE-6000 Series Room Temperature Sensors 12 Applications Guide© 2006 KMC Controls, Inc. AN-0106A-RevB
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
NOTE: For an additional sample application
of programming override timers, adapt
the information in the Application Note
AN0504F Programming Override Timers
section of the the Digital Designer’s Guide
(SP-022).
NOTE: For Celsius, use these lines for 10 through
30 instead.
10 REM *** SETPOINT RANGE FOR ROOM SENSOR
***
20 REM *** RANGE IS 4 - 32 DEGREES CEL-
SIUS ***
30 AV2 = AI2 / 0.17857 + 4
9. Click Send.
10. Click OK.
11. Click Yes for “Execute Program Now?”
12. Click Close.
13. Click OK.
Optional Control Basic (STE-6012/6016 only)
1. In the BACstage soware main menu, select
Objects > BASIC Programs.
2. Click Edit.
3. Type in a name in the Description eld and/or
Label eld.
4. Click Autorun.
5. Click End Edit.
6. Click Yes for “Send Update Notication Now?”
7. Click once in the # column.
8. Type in program lines (see the following
example).
NOTE: This is only an example. Details need to
t the controller conguration.
10 REM *** SETPOINT RANGE FOR ROOM SEN-
SOR ***
20 REM *** RANGE IS 40 - 90 DEGREES
FAHRENHEIT ***
30 AV2 = AI2 / 0.1 + 40
40 REM *** AV2 IS THE ROOM SETPOINT
(FROM LINE 1 IN ANALOG VALUE OBJECT
SCREEN) ***
50 REM *** AI2 IS SETPOINT VOLTAGE FROM
SENSOR (FROM LINE 2 IN INPUT OBJECT
SCREEN) ***
60 REM *** AI1 IS TEMPERATURE VOLTAGE
FROM SENSOR (FROM LINE 1 IN INPUT
OBJECT SCREEN) ***
70 REM *** BV2 IS THE OVERRIDE (FROM
LINE 2 IN BINARY VALUE OBJECT
SCREEN) ***
80 REM *** USE BUTTON ON SENSOR TO
START OVERRIDE (BV2) ***
90 IF SENSOR-ON( AI1 ) OR SENSOR-OFF(
AI1 ) THEN START BV2
100 IF TIME-ON( BV2 ) > 2:00:00 THEN
STOP BV2
110 END
NOTE: The STE-6012/6016 is powered by the
controller on terminal D or the green wire.
With 7.5 VDC applied, the sensor is in
setback/setup mode; with 12 VDC applied,
the sensor is in normal/override mode.
Pressing the Down buon momentarily
sends 0 VDC to the controller for a
SENSOR-ON signal; pressing the Up buon
sends greater than 5 VDC for a SENSOR-
OFF signal. When in normal/override
mode, pressing the Down or Up buon
raises or lowers the setpoint voltage. When
in setback/setup mode, pressing either
buon selects override mode.