Setting range is from 5min
to 900min. Increment of
each click is 5min.
Battery equalized timeout
Setting range is from 5min
to 900 min. Increment of
each click is 5 min.
Setting range is from 0 to 90
days. Increment of each
click is 1 day
Equalization activated
immediately
If equalization function is enabled in program 33, this program
can be set up. If “Enable” is selected in this program, it’s to
activate battery equalization immediately and LCD main page
will shows “ ”. If “Disable” is selected, it will cancel
equalization function until next activated equalization time
arrives based on program 37 setting. At this time, “ ” will
not be shown in LCD main page.
Reset all stored data for PV
generated power and
output load energy
Firmware upgrade for USB
On-the-Go function
Upgrade disable (Default)
Re-write USB internal
parameter
Re-write function disable
(Default)
Export log function disable
(Default)
Export log function enable
Reset log function disable
Reset log function enable
Data log recorded interval
*The maximum data log
number is 1440. If it’s over
1440, it will overwrite as
first log.
For minute setting, the
range is from 00 to 59.