19
22
Beeps while primary
source is interrupted
Alarm on (Default)
Alarm off
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable (Default)
Bypass enable
25
Record Fault code
Record enable
Record disable (Default)
26
Bulk charging voltage
(C.V voltage)
default setting: 56.4V
If self-defined is selected in
program 5, this program can be
set up. Setting range is from 48.0V
to 64.0V. Increment of each click is
0.1V.
27
Floating charging voltage
default setting: 54.0V
If self-defined is selected in
program 5, this program can be
set up. Setting range is from 48.0V
to 64.0V. Increment of each click
is 0.1V.
28
AC output mode
*This setting is able to set
up only when the inverter
is in standby mode, Be
sure that on/off Switch is
in ”OFF” status.
Single: This inverter is used
in single phase application.
Parallel: This inverter is operated
in parallel system.
L1 phase:
L2 phase: