Obtain the APECS Programming Interface Harness Kit GM100177-KP1.
Required for electronic governor functionality; access via Kohler Power Resource Center.
Required for electronic governor functionality; access via Kohler Power Resource Center.
Includes 8 mm wrenches, TP Torx Plus® driver, and flex joint/universal joint.
Disconnect battery cables, remove negative lead first, reconnect negative last.
Press OFF/RESET, disconnect battery charger, remove battery cables (negative first).
Avoid flames/sparks near fuel system; catch fuels in approved container.
Shut down generator, disconnect charger, disconnect battery cables.
Clean area, remove old governor, install new actuator carefully to avoid runaway.
Install new cover seal, position actuator, align mounting holes, connect leads to actuator screws.
Install new O-ring on return line connector, apply grease, and install fuel return line.
Remove air cleaner cover, element, and base for safety during installation.
Mount electronic governor in junction box, connect governor harness to terminal strip.
Connect grey male connector to governor, grey female to existing harness, 7N and P terminals to TB12.
Connect USB connector on harness to PC, use USB cable to connect PC to generator controller.
Change ECM Model to Woodward APECS ECM using SiteTech™ software.
Turn the toggle switch on the interface harness to ON (1).
Start Kohler ACT Tool, accept license, select calibration file, and download.
Start generator, access Actuator Throttle Arm screen, adjust screws for target RPM.
Turn interface harness toggle to OFF, then press OFF/RESET on controller.
Disconnect harness, unplug female connector, plug connector into electronic governor.
Replace air cleaner base, element, and cover.
Replace junction box cover, disconnect battery for 5 mins, reconnect battery and charger.
Follow standard procedure: shut down, disconnect charger, disconnect battery.
Measure coil resistance (2.05 ±0.25 ohms) and isolation (>3 Megohm).
Manually move actuator through range; check for binding or sticking.
Apply 12 VDC to actuator with diode; check for smooth full-fuel position operation.