TP-6727 10/1138 Section 5 Controller
then step through the following parameters. Use the up
(
) and down () arrow buttons to select the appropriate
setting for the application.
Note: Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the master switch is
moved to the OFF/RESET position.
Voltage/frequency setting (Uu). Select the system
voltage and frequency from the table in Figure 5-1.
Note: This parameter sets the nominal system voltage
and frequency. To adjust the output (measured)
voltage, see Section 5.1.
Unit configuration (Uc). This parameter sets the
generator set type. Select Uc01, standby.
Engine configuration (Ec). The engine configuration
must match the generator set engine type.
Advanced configuration mode (Adnc). The data
input types, battery voltage, and communications
setting can be changed in the advanced configuration
mode. Press the up arrow button when Adnc is
displayed to enter the advanced configuration mode.
Engine data input types (Ed). This setting defines the
type of senders used on the generator set engine.
Battery voltage (Bt). This setting toggles between 12
and 24 VDC for the engine starting battery voltage.
Communications setting (Cn). This setting allows the
user to set the controller for communication with
optional meters. The factory setting is Cn00, no CAN
communications. Change this setting if necessary. See
Figure 5-1.
CANbus address (CA). This parameter sets the
CANbus address for the controller. The CA parameter
appears only on models with engines equipped with
ECMs.
Parameter Setting
Description
Voltage, VAC Frequency, Hz Phases, Wires Connection
Unit’s system voltage
and frequency
Uu01 120/240 60 Single phase, 3 wire 1 phase
Uu04 277/480 60 Three phase, 4 wire Wye
Uu10 120/240 60 Three phase, 4 wire Delta
Uu10 139/240 60 Three phase, 4 wire Wye
Uu11 120/208 60 Three phase, 4 wire Wye
Uu16 127/220 60 Three phase, 4 wire Wye
Unit configuration Uc01 Standby
Engine type Ec11 * 30REYG
Ec12 * 15REYG
Engine data input types Ed01 15/30REYG factory setup
Battery voltage Bt12 12 VDC
Communications Cn00 No CAN communications, 48-hour power down (factory setting)
Cn01 J1939 communications, no power down
Cn06 Enables J1939 communications and 1-hour ADC power down after engine stop
for either:
a. Remote start/stop switch
b. Automatic transfer switch
CANbus address CA01 15/30REYG
* ADC application program version 3.25 or higher is required
Figure 5-1 Configuration Parameters