TP-6953 7/19 65Section 2 Operation
SiteTecht Parameter
Write
Access
Units
Decision-Maker
r
3500
User Interface
Notes
Voltage Selector Switch
Voltage Selector Switch Position
Not supported for these models.
Voltage Selector Switch Max Positions
Voltage Selector Switch Position 1 Voltage
Voltage Selector Switch Position 1 Frequency
Voltage Selector Switch Position 1 Voltage Phase
Connection
Voltage Selector Switch Position 2 Voltage
Voltage Selector Switch Position 2 Frequency
Voltage Selector Switch Position 2 Voltage Phase
Connection
Voltage Selector Switch Position 3 Voltage
Voltage Selector Switch Position 3 Frequency
Voltage Selector Switch Position 3 Voltage Phase
Connection
Genset System Configuration
Genset System Voltage Stopped V System Voltage L- L: ###V The generator operating
voltage
Genset System Frequency Stopped Hz System Frequency: ##.#Hz The generator operating
frequency
Genset Voltage Phase Connection Stopped System Phase: Single/Single
Dog/Three-Wye/ Three-Delta
The generator number of
phases (single or three)
Genset Power Rating Locked kW kW Rating: ####kW The generator operating
power rating in kW
Genset Apparent Power Rating Stopped kVA The generator operating
apparent power rating in
kVA
Genset Rated Current None A Rated Current: ###A Calculated from power
rating, voltage, and
connection
Genset System Battery Voltage Stopped V Battery Voltage: ##V The generator operating
battery voltage
Prime Power Application Locked Operating Mode: Standby/Prime Indicates whether the
generator set is in a
prime power application
Current Transformer R atio Locked
Local Start Mode Not supported for these models.
Measurement System Always Units: Metric/English Indicates whether to use
the English or Metric
measurements system
for display of parameter
values and their units
Alarm Silence Always Allowed Always Alarm Silence: Always/Auto Only When true, the alarm can
be silenced when the
controller is in any state;
when false, the alarm can
only be silenced in the
Auto state
NFPA 110 Enabled Always NFPA Defaults: On/Off Indicates whether
NFPA110 defaults are
enabled
Cool Down Temperature Override Always Cooldown Override: On/Off Indicates whether the
engine’s cooled-down
parameter should be
overridden during the
time delay
Oil Sensor Type Stopped Indicates the type of oil
sensor
Public CAN Protocol Not supported for these models.
Display Contrast Always Contrast: ###
Using Voltage Selector Switch Stopped
Genset System Language Always Language: English
Genset Maximum Percent Capacity Always %
Generator Overloaded Percent Always %
Under Frequency Shed Level Always %
Base Load Add Time Always s
Base Over Load Shed Time Always s
Base Under Frequency Shed Time Always s