TP-6953 7/1966 Section 2 Operation
SiteTecht Parameter
Write
Access
Units
Decision-Maker
r
3500
User Interface
Notes
Genset Fuel Type Stopped Fuel Type: Natural Gas/LP/
Gasoline/Diesel/ Unknown
Battle Mode Always Emergency Battlemode: On/Off
ECM Powered Mode Stopped Indicates whether the
ECM Power is turned on
Genset Application Locked Application Type: None/Marine/
Mobile/Standby/Prime
Genset Calibration
Calibration Factor Voltage L1-L2 Always Gen L1- L2 Volts: ###.#V
Calibration Factor Voltage L2-L3 Always Gen L2- L3 Volts: ###.#V
Calibration Factor Voltage L3-L1 Always Gen L3- L1 Volts: ###.#V
Calibration Factor Voltage L1-N Alway s Gen L1- L0 Volts: ###.#V
Calibration Factor Voltage L2-N Alway s Gen L2- L0 Volts: ###.#V
Calibration Factor Voltage L3- N Always Gen L3- L0 Volts: ###.#V
Calibration Factor Current L1 Always Gen L1 Current: ###.#A
Calibration Factor Current L2 Always Gen L2 Current: ###.#A
Calibration Factor Current L3 Always Gen L3 Current: ###.#A
Bus Calibration Factor Voltage L1-L2 Always Bus L1- L2 Volts: ###.#V
Bus Calibration Factor Voltage L2-L3 Always Bus L2- L3 Volts: ###.#V
Bus Calibration Factor Voltage L3-L1 Always Bus L3- L1 Volts: ###.#V
Voltage Regulator
Voltage Regulator Average Voltage Adjustment Always V Voltage Adjust: ###.#V The target voltage setting
Voltage Regulator Volts Per Hertz Slope Always % V/Hz Slope: ##%/Hz The ratio of volts/hertz
ramping
Voltage Regulator Volts Per Hertz Cut In Frequency Always Hz V/Hz Setpoint: ##.#Hz The frequency that the
VoltsPerHertzfeatureis
activated
Voltage Regulator Gain Always Voltage Gain Adjust: ### Provides adjustment to
the sensitivity of the
voltage regulator
Voltage Regulator Stability Adjust Always Controls damping to
provide stable voltage
during transients and
steady-state operation
Voltage Regulator Firmware Version Not supported for these models.
Voltage Regulator Target Voltage None V Target Voltage: ###.#V
Voltage Regulator Normal Ramp Rate Always %/s Start Up Ramp Rate: ###.#%/s
Engine Timing
Engine Idle Duration Always s The length of time for the
engine idle mode
Engine Restart Delay Always s The length of time to wait
before attempting to
restart the engine when
engine rotation cannot be
determined
Engine Start Delay Always s Engine Start Delay: ##s The length of time to wait
before attempting to start
the engine after a remote
start command is
received
Engine ECM Start Delay Always s The length of time to wait
before engaging the
starter after the ECM has
been powered
Engine Cool Down Delay Always s Cooldown Delay: ##s The length of time to wait
before stopping the
engine after a remote
stop command is
received (unless the low
temperature delay
applies)
Engine Start Aid Delay Always s Starting Aid Delay: ##s The length of time to turn
the starting aid output on
before attempting to start
the engine
Engine Crank On Delay Always s Crank On Delay: ##s The length of time for the
on-period of the crank
cycle