TP-6735 7/17 Appendix 117
Appendix F Controller Parameters (SiteTech)
The following table lists controller parameters that can
be viewed and adjusted using Kohlerr SiteTecht
software. The Access column in the table shows which
parameters can only be viewed (Read or Locked), and
which parameters c an be changed using the software
(Write).
Parameters are factoy-set according to the generator
set model. Use SiteTech to change settings if
necessary during service or after controller
replacement.
Group Parameter Access Units
Adjustment
Range
Default Setting
Identity
Vendor Read — Kohler Company
Product Read — RDC (38)
Firmware Version Read — —
Engine Metering
Engine Speed Read R/min — —
Engine Target Speed Read R/min — —
Battery Voltage Read V — —
Lube Oil Temperature Read _C — —
Genset Controller Temperature Read _C — —
Engine Speed
Governor
Engine Speed Adjustment Write 0--99 50
Engine Speed Gain Adjustment Write 0--99 50
Generator Metering
Generator Voltage L1-L2 Read V — —
Generator Frequency Read Hz — —
Generator Metering Firmware Version Read — —
Genset Info
Genset Model Number Write — *
Genset Serial Number Write — *
Alternator Part Number Write — *
Engine Part Number Write — *
Engine Model Number Write — *
Engine Serial Number Write — *
Genset State Read — Off (0)
Genset Run Time
Genset Controller Total Operation
Time
Read h — —
Engine Total Run Time Read h — —
Engine Total Run Time Loaded Read h — —
Engine Total Number Of Starts Read — —
Genset Personality
Profile
Engine Number Of Flywheel Teeth Locked — —
Engine Cooled Down Temperature Locked _C — 65
Engine Crank Disconnect Speed Read R/min — —
Engine Run Speed Locked R/min — —
Genset System
Configuration
Genset System Voltage Write V 110--600 *
Genset System Frequency Write Hz 50/60 60
Genset Voltage Phase Connection Write 0--3 *
Genset System Battery Voltage Locked V 12/24 12
Measurement System Write English (0)
Metric (1)
English (0)
* Factory set. Enter these numbers on a new controller after controller replacement.