TP-6735 7/17118 Appendix
Group Default Setting
Adjustment
Range
UnitsAccessParameter
Voltage Regulator
Voltage Regulator Average Voltage
Adjustment
Write V 108--660 *
Voltage Regulator Volts Per Hertz
Slope
Write % 1--10 5
Voltage Regulator Volts Per Hertz Cut
In Frequency
Write Hz 42--62 57.5
Voltage Regulator Gain Write 1--255 128
Voltage Regulator Firmware Version Read — —
Engine Timing
Engine Start Delay Write s 0--300 0
Engine Cool Down Delay Write s 0--600 300
Engine Crank On Delay Write s 10--30 15
Engine Crank Pause Delay Write s 1--60 15
Engine Number Of Crank Cycles Write 1--6 3
Genset Protection
After Crank Disconnect Fault Inhibit
Delay
Read s — 30
Genset Low Battery Voltage Warning
Delay
Read s — 90
Genset High Battery Voltage Warning
Delay
Read s — 10
Genset Low Battery Voltage Warning
Limit
Write % 80--105 100
Genset High Battery Voltage Warning
Limit
Write % 110--135 125
Genset Battery Low Cranking Voltage
Warning Delay
Read s — 6
Genset Battery Low Cranking Voltage
Warning Limit
Read % — 60
Engine Protection
Engine High Oil Temperature
Shutdown Delay
Read s — 5
Engine Low Oil Pressure Shutdown
Delay
Read s — 5
Engine Locked Rotor Shutdown Delay Write s 1-- 5 5
Genset Low Engine Speed Shutdown
Limit
Write % 75--95 85
Genset High Engine Speed Shutdown
Limit
Write % 105--120 115
Generator Protection
Loss Of AC Sensing Shutdown Delay Read s — 3
Genset Low Voltage Shutdown Delay Write s 5--30 10
Genset High Voltage Shutdown Delay Write s 2-- 10 2
Genset Low Voltage Shutdown Limit Write % 70--95 80
Genset High Voltage Shutdown Limit Write % 105--135 120
Genset Short Term Low Frequency
Shutdown Delay
Read s — 10
Genset Long Term Low Frequency
Shutdown Delay
Read s — 60
Genset High Frequency Shutdown
Delay
Read s — 10
Genset Low Frequency Shutdown
Limit
Write % 80--95 90
Genset High Frequency Shutdown
Limit
Write % 102--140 110
* Factory set. Enter these numbers on a new controller after controller replacement.