TP-6735 7/17 Appendix 119
Group Default Setting
Adjustment
Range
UnitsAccessParameter
ATS Metering
Summary
ATS Contactor Position Read
ATS Sources Available Read
Source 1 Metering
Source 1 Voltage L1-L2 Read V
Source 1 Voltage Average Line To
Line
Read V
ATS Connection
Configuration
ATS Source Read
Source 1 System
Configuration
Source 1 System Voltage Write V 110--600 240
Source 1 System Frequency Write Hz 48--62 60
Source 1 Voltage Debounce Delay Write s 0.1 --9.9 0.5
Source 1 Low Voltage Pickup Write % 85--100 90
Source 1 Low Voltage Dropout Write % 75--98 90
Source 1 Calibration Source 1 Calibration Factor Voltage
L1-L2
Write 0.65--1.5 1.0
Source 2 System
Configuration
Source 2 Voltage Debounce Delay Write s 0.1 --9.9 0.5
Source 2 Low Voltage Pickup Write % 85--100 90
Source 2 Low Voltage Dropout Write % 75--98 90
ATS Exercise
Exercise Interval Write Weekly (5)
2 Weeks (6)
Weekly (5)
Exercise Run Duration Write min 10--30 20
Exercise Mode Write Unloaded (1)
Economy (2)
Loaded (3)
Unloaded (1)
ATS Delays
ATS Transfer From Preferred Delay Write s 1-- 10 3
ATS Transfer From Standby Delay Write s 1--600 120
ATS Source 2 Engine Start Delay Write s 1--10 3
Network
Configuration
(for OnCue)
DHCP Enabled Write True/False
Static IP Address Write 0.0.0.0
Static Subnet Mask Write 0.0.0.0
Static Default Gateway Write 0.0.0.0
Static DNS Server 1 Write 0.0.0.0
Static DNS Server 2 Write 0.0.0.0
Server Host Name Write oncue.kohler.com
Network Status
(for OnCue)
IP Address Read 0.0.0.0
Subnet Mask Read 0.0.0.0
Default Gateway Read 0.0.0.0
DNS Server 1 Read 0.0.0.0
DNS Server 2 Read 0.0.0.0
MAC Address Read
Connected Server IP Address Read 0.0.0.0
Network Connection Established Read