Residential/Commercial Generator Sets
Models:
14RESA/RESAL
20RESA/RESAL
20RESB
20RESC/RESCL
20RESD
Controllers:
RDC2 Controller
DC2 Controller
TP-6805 8/15b
Service

Table of Contents

Other manuals for Kohler 20RESB

Questions and Answers

  • B
    beltranbrianSep 10, 2025
    Why does my Kohler Portable Generator experience Main Power Overload Shutdown?
    • J
      Joseph MejiaSep 12, 2025
      The Main Power Overload Shutdown is caused by an overcurrent condition on the DC power supply circuit. Check the crank, run, and flash relay circuits for short circuits. To address nuisance shutdowns, update the controller firmware to version 6.7 or higher.
  • A
    Anthony KingSep 12, 2025
    What to do if my Kohler 20RESB shows a fault shutdown?
    • R
      Ronald MitchellSep 12, 2025
      If your Kohler Portable Generator displays a fault shutdown message on the controller, identify and correct the cause of the fault condition. Then, press the OFF button on the controller to clear the fault.
  • F
    fpowellSep 14, 2025
    What to do if the thermostat tripped on my Kohler 20RESB?
    • M
      Michael WilliamsSep 14, 2025
      If the thermostat trips on your Kohler Portable Generator, check for blocked air inlets and exhaust outlets. Then, follow the instructions to reset the thermostat.
  • J
    Joshua DouglasSep 15, 2025
    How to fix engine hunting on Kohler Portable Generator models 20RESA(L) and 20RESC(L)?
    • M
      Michaela GonzalezSep 16, 2025
      To address engine hunting in Kohler Portable Generator models 20RESA(L) and 20RESC(L), update to the most current version of firmware available. Also, install vent tubes on the two reference ports on the fuel regulator.
  • C
    Christopher TaylorSep 18, 2025
    What to do if my Kohler 20RESB Portable Generator has an Over Crank fault?
    • K
      Kayla MoralesSep 18, 2025
      If your Kohler Portable Generator experiences an Over Crank fault, check the fuel supply, cranking circuit, and cranking battery. You may also need to troubleshoot the engine.

Kohler 20RESB Specifications

General IconGeneral
Model20RESB
TypePortable Generator
Power Output20 kW
Fuel TypeGasoline / Propane
Starting SystemElectric Start
Voltage120/240V
Frequency60 Hz
Starting Watts (Gasoline)22000 watts
Running Watts (Propane)18000 watts
EngineKohler
Run Time (Gasoline)10 hours at 50% load
Warranty3 years