TP-6907 5/16 35Section 3 Controller
SiteTech Grou p Notes [
Default
Setting
Adjustment
Range *
UnitsParameter
Genset Personality Profile Personality Power Rating 50 Hz
200 400
kW No effect. N/A
Genset Personality Profile Personality Power Rating 50 Hz
190 380
kW No effect. N/A
Genset Personality Profile Personality Power Rating 50 Hz
173 346
kW No effect. N/A
Genset Personality Profile Personality Power Rating 50 Hz
Delta
kW No effect. N/A
Genset Personality Profile Personality Fixed Voltage 60
Hz
V No effect. N/A
Genset Personality Profile Personality Power Rating
SinglePhase60Hz10PF
kW No effect. N/A
Genset Personality Profile Personality Power Rating
Single Phase 60 Hz 8 PF
kW No effect. N/A
Genset Personality Profile Personality Power Rating Fixed
Volt 60 Hz
kW No effect. N/A
Genset Personality Profile Personality Power Rating 60 Hz
240 480
kW No effect. N/A
Genset Personality Profile Personality Power Rating 60 Hz
230 460
kW No effect. N/A
Genset Personality Profile Personality Power Rating 60 Hz
220 440
kW No effect. N/A
Genset Personality Profile Personality Power Rating 60 Hz
208 416
kW No effect. N/A
Genset Personality Profile Personality Power Rating 60 Hz
190 380
kW No effect. N/A
Genset Personality Profile Personality Power Rating 60 Hz
Delta
kW No effect. N/A
Genset Personality Profile Personality Installed Options Locked None N/A
Genset System
Configuration
Genset System Voltage V 110 -- 600 240.0
Genset System
Configuration
Genset System Frequency Hz 50/ 60 60.0
Genset System
Configuration
Genset Voltage Phase
Connection
0--3 Single
Phase
Genset System
Configuration
Genset Power Rating kW 10-- 5000 21
Genset System
Configuration
Genset Rated Current A Read Only Factory set
Genset System
Configuration
Genset System Battery Voltage V 12 / 24 12
Genset System
Configuration
Prime Power Application Standby or prime Standby
Genset System
Configuration
Current Transformer Ratio Locked Factory set N/A
Genset System
Configuration
Local Start Mode Read Only Off
Genset System
Configuration
Measurement System English or metric English
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT with combined interface/ load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.