TT-1715 2/17 13
Digital
Gauge
Display
ADC IId
Display
SiteTech
Display
Description
No faults
47
ERR
Oil Pres Low Shutdwn Low Engine Oil Pressure Shutdown: Low Oil Pressure
47
WARN
Oil Pres Low Warning Low Engine Oil Pressure Wa rning: Low Oil Pressure
53
WARN
Lo Crank Vlt Warning Low Cranking Voltage Warning: Weak Battery
62
ERR
Sea Pressur Low Shutdwn Low Engine Seawater Pressure Shutdown: Sea Pump Pressure
64
ERR
Engine Speed High Shutdwn High Engine Speed Shutdown: Engine Overspeed
65
ERR
Coolant Temp High Shutdwn High Engine Coolant Temperature Shutdown: Coolant Sensor Range High
65
WARN
Coolant Temp High Warning High Engine Coolant Temperature Warning: Coolant Sensor Range High
HB
WARN
Battery High Warning High Battery Voltage Warning: High Battery Voltage
LB
WARN [
Battery Low Warning Low Battery Voltage Warning: Low Battery Voltage
OC
ERR [
Over Crank Shutdwn
Locked Rotor Shutdwn
Over Crank
Locked Rotor
Shutdown: Over Crank or Locked Rotor
AF
ERR [
Aux Input Shutdwn Auxiliary Input Shutdown: Auxiliary Fault Input
OU
ERR
Volts xx--xx High Shutdwn High Generator Voltage xx--xx Shutdown: Over Voltage
UU
ERR
Volts xx--xx Low Shutdwn Low Generator Voltage xx--xx Shutdown: Under Voltage
OF
ERR
Frequency High Shutdown High Generator Frequency Shutdown: Over Frequency
UF
ERR [
Frequency Low Shutdown Low Generator Frequency Shutdown: Under Frequency
ERR * Not available Not available Shutdown: Unknown/Not Supported Shutdown
WARN * Not available Not available Warning: Unknown/Not Supported Warning
1000
ERR *
Not available Not available ECU Data Loss (generated by gauge)
1001
ERR *
Not available Not available Start Fault (generated by gauge)
1002
ERR *
Not available Not available Stop Fault (generated by gauge)
* Fault generated by the digital gauge.
[ Check the controller’s display to see more detailed information regarding the fault. See Section 16.