159Section 8 Component Testing and AdjustmentTP-6356 4/12
Model Engine
Governor
Type
High Coolant Temp.
Fault Warning
Low Coolant Temp,
Fault Warning
Low Oil Pressure
Fault Warning
Test Connections Test Connections Test Connections
Gas
25--150RZG/RZGB GM
Electronic 2
A--BLK (TB2-16)
B--RED (TB2-2)
C--WHT (TB2-1)
1 Lead 35A 2
A--BLK (TB2-4)
B--RED (TB2-18)
C--WHT (TB2-3)
200--275RZDB DDC Gas
400--800RZW Waukesha
Diesel
20ROZJ
John Deere
Mechanical
2
A--BLK (TB2-16)
B--RED (TB2-2)
C--WHT (TB2-1)
1 Lead 35A 2
A--BLK (TB2-4)
B--RED (TB2-18)
C--WHT (TB2-3)
20ROZJ
Electronic
20/30REOZJC
20--230REOZJB Mechanical
20--230REOZJB Electronic
200REOZPB DDC Series 40 Electronic 2
A--BLK (TB2-16)
B--RED (TB2-2)
C--WHT (TB2-1)
1 Lead 35A 2
A--BLK (TB2-4)
B--RED (TB2-18)
C--WHT (TB2-3)
600--2000REOZM*
Mitsubishi Electronic 2
A--BLK (TB2-16)
B--RED (TB2-2)
C--WHT (TB2-1)
1 Lead 35A 2
A--BLK (TB2-4)
B--RED (TB2-18)
C--WHT (TB2-3)
600--2000REOZMB*
750--2000REOZMD[
750--2000ROZMC[
* Applies to Decision-Makerr 550 and 6000 controllers.
[ Applies to Decision-Makerr 550, 3000, and 6000 controllers.
BLK Black; BLU Blue; BRN Brown; GRY Gray; GRN Green; ORG Orange; PNK Pink; WHT White
Figure 8-64 Fault Warning Test Method for Decision-Makerr 550 Controllers without Engine ECM Control
Model Engine Governor Type
High Coolant Temp.
Fault Shutdown
Low Oil Pressure
Fault Shutdown
Test Connections Test Connections
Gas
25--150RZG/RZGB GM
Electronic 2
A--BLK (TB2-16)
B--RED (TB2-2)
C--WHT (TB2-1)
2
A--BLK (TB2-4)
B--RED (TB2-18)
C--WHT (TB2-3)
200--275RZGB DDC Gas
400--800RZW Waukesha
Diesel
20ROZJ
John Deere
Mechanical
2
A--BLK (TB2-16)
B--RED (TB2-2)
C--WHT (TB2-1)
2
A--BLK (TB2-4)
B--RED (TB2-18)
C--WHT (TB2-3)
20ROZJ Electronic
20/30REOZJC Electronic
20--230REOZJB Mechanical
20--230REOZJB Electronic
200REOZPB DDC Series 40 Electronic 2
A--BLK (TB2-16)
B--RED (TB2-2)
C--WHT (TB2-1)
2
A--BLK (TB2-4)
B--RED (TB2-18)
C--WHT (TB2-3)
600--2000REOZM*
Mitsubishi Electronic 2
A--BLK (TB2-16)
B--RED (TB2-2)
C--WHT (TB2-1)
2
A--BLK (TB2-4)
B--RED (TB2-18)
C--WHT (TB2-3)
600--2000REOZMB*
750--2000REOZMD[
750--2000ROZMC[
* Applies to Decision-Makerr 550 and 6000 controllers.
[ Applies to Decision-Makerr 550, 3000, and 6000 controllers.
BLK Black; BLU Blue; BRN Brown; GRY Gray; GRN Green; ORG Orange; PNK Pink; WHT White
Figure 8-65 Fault Shutdown Test Method for Decision-Makerr 550 Controllers without Engine ECM Control