How to fix a faulty Kohler APM402?
- TTaylor JonesOct 24, 2025
If the Kohler Controller master control button is in the OFF/RESET mode, press the controller master control RUN or AUTO button. In case of controller circuit board(s) inoperative, controller master control buttons inoperative, replace the controller or the controller master control button circuit board. If the controller fuse is blown, check for continuity across the fuse and troubleshoot the controller wiring and replace the circuit board, or if the voltage regulation is inoperative, replace the junction box sensing fuses. For a controller firmware error, review the controller display troubleshooting chart. If the engine start circuit is open, press the controller master control RUN button to test the generator set and troubleshoot the auto start circuit and the time delays. In case of c...