TP-6694 2/25 137
Connect to the normally open (NO) or normally closed (NC) terminals as required for each accessory. The relay contacts (K1 to
K14) are rated:
• 10 amp @ 120 VAC
• 10 amp @ 28 VDC (max.)
• 0.01 amp @ 28 VDC (min.)
The common fault relay contact (K15) is rated:
• 500 mA @ 125 VAC
• 2 amp @ 30 VDC
Figure 72 4-Input/15-Output Module Customer Connections
Connections
Leads 42A and 2 provide power to the relays. Do not use terminals 42A (+) or 2 (GND) on the controller connection kit terminal
strip to supply voltage to user-supplied accessories. User-supplied DC accessories require separate leads connected directly to
the battery for the voltage supply. Attach user-supplied 12/24-volt DC accessories to the battery positive (+) connection at the
starter solenoid and to the battery negative (-) connection at the engine ground. The 120 VAC accessories require a user-
supplied voltage source.
Note:
A maximum of three inputs may be connected to a single relay driver output. Inputs include dry contacts, remote annunciator,
common failure alarm, A/V alarm, and shunt trip line circuit breaker.
Note:
Only one 4-input/15-output module can be connected to the controller.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the
negative (–) lead first when disconnecting the battery. Reconnect the negative (–)
lead last when reconnecting the battery.
P35 4-position jack connects to controller
(factory-connected)
TB5 output connections C and NO for the common
fault relay K15 (other TB5 terminals are factory
connections only)
TB6 8-position terminal block,
digital inputs/digital returns
(D11, D12, D13 and D14)
P36 8-position pin,
analog inputs
TB7 through TB13, connections for relays K1 through K14 with
Normally Open (NO) and Normally Closed (NC) contacts
Battery positive (+) connections (TB5-42A)
CAN connections (TB5-CAN (+)/-CAN (-)
Battery negative (-) connections (TB5-2)